| Date |
Text |
| 2013-05-07 11:46:02 | 5305 GREENWOOD AVENUE - SUITE #101 |
| | PERMIT #13040386 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | REVIEW #2: SHEET A-0.1 NOT RESUBMITTED SHOWING THE |
| | CORRECT ADDRESS AND SUITE NUMBER MATCHING THE PERMIT |
| | APPLICATION. |
| | ORIGINAL COMMENT: SHEET A-0.1: THE PERMIT APPLICATION |
| | INDICATES THE PROJECT ADDRESS TO BE 5305 GREENWOOD |
| | AVENUE - SUITE #101; HOWEVER, THE PLANS INDICATE AN |
| | ADDRESS OF 5325 GREENWOOD AVENUE - SUITE #201. |
| | |
| | REVIEW #2: SATISFIED |
| | ORIGINAL COMMENT: SHEET A-1.1: DOORS SERVING AN |
| | OCCUPANT LOAD OF 50 OR MORE PERSONS SHALL SWING IN THE |
| | DIRECTION OF EGRESS. THIS REQUIREMENT WILL AFFECT DOOR |
| | #201 AND EXISTING STAIRWELL TENANT ENTRY DOOR. NOTE: |
| | THE SWING OF DOOR #201 IS BEING REQUESTED TO SWING IN |
| | THE OPPOSITE DIRECTION BECAUSE THE TWO SETS OF DOUBLE |
| | DOORS (#224 AND "EXISTING") AT THE TENANT ENTRANCE ARE |
| | NOT LOCATED AT LEAST 1/3 THE DIAGONAL DISTANCE TO BE |
| | CONSIDERED SEPARATED EXITS. |
| | |
| | REVIEW #2: REVISED SHEET E2.1 NOT SUBMITTED. |
| | ORIGINAL COMMENT: SHEET E2.1: REMOVE THE INDICATING |
| | ARROW FROM THE EXIT SIGN LOCATED ABOVE DOOR #201. NOTE: |
| | THE SECONDARY EXIT FROM THIS SPACE IS THE STAIRWELL |
| | TENANT ENTRY DOOR. |
| | |
| | REVIEW #2: REVISED SHEET FA2.1 NOT SUBMITTED. |
| | ORIGINAL COMMENT: SHEET FA2.1: NO FIRE ALARM |
| | NOTIFICATION APPLIANCES PROVIDED NEAR CHECK OUT #231 OR |
| | ADULTS WAITING AREA #224 |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |