2013-05-07 11:46:025305 GREENWOOD AVENUE - SUITE #101
 PERMIT #13040386
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REVIEW #2: SHEET A-0.1 NOT RESUBMITTED SHOWING THE
 CORRECT ADDRESS AND SUITE NUMBER MATCHING THE PERMIT
 APPLICATION.
 ORIGINAL COMMENT: SHEET A-0.1: THE PERMIT APPLICATION
 INDICATES THE PROJECT ADDRESS TO BE 5305 GREENWOOD
 AVENUE - SUITE #101; HOWEVER, THE PLANS INDICATE AN
 ADDRESS OF 5325 GREENWOOD AVENUE - SUITE #201.
  
 REVIEW #2: SATISFIED
 ORIGINAL COMMENT: SHEET A-1.1: DOORS SERVING AN
 OCCUPANT LOAD OF 50 OR MORE PERSONS SHALL SWING IN THE
 DIRECTION OF EGRESS. THIS REQUIREMENT WILL AFFECT DOOR
 #201 AND EXISTING STAIRWELL TENANT ENTRY DOOR. NOTE:
 THE SWING OF DOOR #201 IS BEING REQUESTED TO SWING IN
 THE OPPOSITE DIRECTION BECAUSE THE TWO SETS OF DOUBLE
 DOORS (#224 AND "EXISTING") AT THE TENANT ENTRANCE ARE
 NOT LOCATED AT LEAST 1/3 THE DIAGONAL DISTANCE TO BE
 CONSIDERED SEPARATED EXITS.
  
 REVIEW #2: REVISED SHEET E2.1 NOT SUBMITTED.
 ORIGINAL COMMENT: SHEET E2.1: REMOVE THE INDICATING
 ARROW FROM THE EXIT SIGN LOCATED ABOVE DOOR #201. NOTE:
 THE SECONDARY EXIT FROM THIS SPACE IS THE STAIRWELL
 TENANT ENTRY DOOR.
  
 REVIEW #2: REVISED SHEET FA2.1 NOT SUBMITTED.
 ORIGINAL COMMENT: SHEET FA2.1: NO FIRE ALARM
 NOTIFICATION APPLIANCES PROVIDED NEAR CHECK OUT #231 OR
 ADULTS WAITING AREA #224
  