Plan Review Notes
Plan Review Notes For Permit 13040386
Permit Number 13040386
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-04-18 08:35:175305 GREENWOOD AVENUE - SUITE #101
 PERMIT #13040386
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-0.1: THE PERMIT APPLICATION INDICATES THE
 PROJECT ADDRESS TO BE 5305 GREENWOOD AVENUE - SUITE
 #101; HOWEVER, THE PLANS INDICATE AN ADDRESS OF 5325
 GREENWOOD AVENUE - SUITE #201.
  
 SHEET A-1.1: DOORS SERVING AN OCCUPANT LOAD OF 50 OR
 MORE PERSONS SHALL SWING IN THE DIRECTION OF EGRESS.
 THIS REQUIREMENT WILL AFFECT DOOR #201 AND EXISTING
 STAIRWELL TENANT ENTRY DOOR. NOTE: THE SWING OF DOOR
 #201 IS BEING REQUESTED TO SWING IN THE OPPOSITE
 DIRECTION BECAUSE THE TWO SETS OF DOUBLE DOORS (#224
 AND "EXISTING") AT THE TENANT ENTRANCE ARE NOT LOCATED
 AT LEAST 1/3 THE DIAGONAL DISTANCE TO BE CONSIDERED
 SEPARATED EXITS.
  
 SHEET E2.1: REMOVE THE INDICATING ARROW FROM THE EXIT
 SIGN LOCATED ABOVE DOOR #201. NOTE: THE SECONDARY EXIT
 FROM THIS SPACE IS THE STAIRWELL TENANT ENTRY DOOR.
  
 SHEET FA2.1: NO FIRE ALARM NOTIFICATION APPLIANCES
 PROVIDED NEAR CHECK OUT #231 OR ADULTS WAITING AREA
 #224
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  