| Plan Review Notes For Permit 13040367 |
| Permit Number |
13040367 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-16 13:41:16 | 5-16-13 | | | | | | 1. PER NEC 406.11, ALL REQUIRED RECEPTACLES MUST BE | | | TAMPER RESISTANT | | | 2. PER NEC 680.74, BOND ALL METAL PIPING AND PARTS IN | | | CONTACT WITH WATER AND CIRCULATOR PUMP | | | 3. PER NEC 680.22B. POOL EQUIPMENT CIRCUIT, AS SHOWN IN | | | L-26/28, MUST USE GFCI BREAKER | | | VB |
|