 1. PER NEC 406.11, ALL REQUIRED RECEPTACLES MUST BE
 TAMPER RESISTANT
 2. PER NEC 680.74, BOND ALL METAL PIPING AND PARTS IN
 CONTACT WITH WATER AND CIRCULATOR PUMP
 3. PER NEC 680.22B. POOL EQUIPMENT CIRCUIT, AS SHOWN IN
 L-26/28, MUST USE GFCI BREAKER
 VB