| Plan Review Notes For Permit 13040367 |
| Permit Number |
13040367 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-29 15:38:57 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WITH A | | | REQUIRED MINIMUM FINISH FLOOR ELEVATION OF 7.5 FEET. AN | | | ELEVATION CERTIFICATE WILL BE REQUIRED. FBC R322.1 | | | | | | 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY | | | CALCULATION FORMS. FBC ENERGY 405.4 | | | | | | 3) SPECIFY THE FASTENING OPTION, DESIGN PRESSURE THAT | | | WILL BE USED ON THE PRODUCT APPROVAL FOR THE BUILT UP | | | ROOFING FL 741-R6 (NOA 12-0601.12). SUBMIT SIGNED AND | | | SEALED RAS 117 CALCULATIONS FOR ENHANCED FASTENING AT | | | THE PERIMETER AND CORNER ROOF AREAS. SEE LIMITATION #7 | | | OF THE NOA. DCA RULE 9N-3 AND FBC R905.1 | | | | | | 4) SPECIFY THE DESIGN PRESSURE, ANCHOR TYPE, ANCHOR | | | SPACING, EDGE DISTANCE, SPAN, ETC. BY CIRCLING THE | | | APPROPRIATE ITEMS IN THE TABLES ON PAGES 5-7 OF THE | | | STORM PANEL PRODUCT APPROVAL DRAWINGS OR ON AN | | | INSTALLATION SCHEDULE. FBC R301.2.1.2 | | | | | | 5) SUBMIT THE PRODUCT EVALUATION REPORT FOR THE ICYNENE | | | SPRAY FOAM INSULATION. FBC R316 | | | | | | NOTE: A SEPARATE PERMIT, APPLICATION AND REVIEW IS | | | REQUIRED FOR A POOL PERMIT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|