Plan Review Notes
Plan Review Notes For Permit 13040367
Permit Number 13040367
Review Stop B
Sequence Number 1
Notes
Date Text
2013-05-29 15:38:572010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WITH A
 REQUIRED MINIMUM FINISH FLOOR ELEVATION OF 7.5 FEET. AN
 ELEVATION CERTIFICATE WILL BE REQUIRED. FBC R322.1
  
 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORMS. FBC ENERGY 405.4
  
 3) SPECIFY THE FASTENING OPTION, DESIGN PRESSURE THAT
 WILL BE USED ON THE PRODUCT APPROVAL FOR THE BUILT UP
 ROOFING FL 741-R6 (NOA 12-0601.12). SUBMIT SIGNED AND
 SEALED RAS 117 CALCULATIONS FOR ENHANCED FASTENING AT
 THE PERIMETER AND CORNER ROOF AREAS. SEE LIMITATION #7
 OF THE NOA. DCA RULE 9N-3 AND FBC R905.1
  
 4) SPECIFY THE DESIGN PRESSURE, ANCHOR TYPE, ANCHOR
 SPACING, EDGE DISTANCE, SPAN, ETC. BY CIRCLING THE
 APPROPRIATE ITEMS IN THE TABLES ON PAGES 5-7 OF THE
 STORM PANEL PRODUCT APPROVAL DRAWINGS OR ON AN
 INSTALLATION SCHEDULE. FBC R301.2.1.2
  
 5) SUBMIT THE PRODUCT EVALUATION REPORT FOR THE ICYNENE
 SPRAY FOAM INSULATION. FBC R316
  
 NOTE: A SEPARATE PERMIT, APPLICATION AND REVIEW IS
 REQUIRED FOR A POOL PERMIT.
  