2013-04-10 08:00:28****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW
 COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS
 AND SHOULD BE PROVIDED TO THE OWNER. THE REMOVAL
 INSTRUCTIONS ARE TO BE APPROVED BY THE BUILDING
 OFFICIAL.
  
 2. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
 3. FBC3501.3.5, PROVIDE DOCUMENTATION TO SHOW THAT THE
 FABRIC MEETS THE REQUIREMENT OF NFPA701.
  
 4. FBC 107.2.1, ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. IF THE DOCUMENTS ARE NOT PREPARED BY A DESIGN
 PROFESSIONAL FS471/481, CALCULATIONS FOR STRUCTURAL
 ELEMENTS MAY BE REQUIRED.
  