2013-05-07 15:06:572010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) THE CONDUCTORS BETWEEN THE METER AND THE MAIN
 CIRCUIT IS REQUIRED TO BE 2/0 PER NEC 310.15 (B) (6).
  
 2) ALL RECEPTACLES WITHIN 6 FT OF A WET BAR SINK OR A
 LAUNDRY SINK ARE REQUIRED TO BE GFCI. THE EXCEPTIONS
 ONLY APPLY TO KITCHENS. PER NEC 210.8 (A) (7).
  
 3) THE ELECTRICAL PLANS AND PANEL SCHEDULES SPECIFY
 THREE A/C SYSTEMS AND THE MECHANICAL PLANS ONLY SHOW
 TWO. PLEASE REVISE PLANS TO MATCH. CITY AMENDMENTS
 107.2.1
  