| Plan Review Notes For Permit 13040324 |
| Permit Number |
13040324 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-07 15:06:57 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRIC | | | | | | 1) THE CONDUCTORS BETWEEN THE METER AND THE MAIN | | | CIRCUIT IS REQUIRED TO BE 2/0 PER NEC 310.15 (B) (6). | | | | | | 2) ALL RECEPTACLES WITHIN 6 FT OF A WET BAR SINK OR A | | | LAUNDRY SINK ARE REQUIRED TO BE GFCI. THE EXCEPTIONS | | | ONLY APPLY TO KITCHENS. PER NEC 210.8 (A) (7). | | | | | | 3) THE ELECTRICAL PLANS AND PANEL SCHEDULES SPECIFY | | | THREE A/C SYSTEMS AND THE MECHANICAL PLANS ONLY SHOW | | | TWO. PLEASE REVISE PLANS TO MATCH. CITY AMENDMENTS | | | 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|