 CONDUCTORS IN NIPPLE BETWEEN METER AND MAIN CB SHOULD
 BE 2/0 AS PER NEC 310.15.B.6
  
 ELECTRICAL AND MECHANICAL DRAWINGS DO NO MATCH. IS IT 3
 AC'S OR 2? COORDINATE WITH MECHANICAL
 CONTRACTOR/ENGINEER FOR CORRECT AMOUNT AND CORRECT
 BREAKER SIZES. CHECK AC SCHEDULE AND MATCH WITH PANEL
 SCHEDULE.
  
 ANY RECEPT WITHIN 6 FEET OF BAR SINK MUST BE GFI. THERE
 ARE NO EXCEPTIONS LISTED FOR THIS FOR BEHIND EQUIPMENT.
 NEC 210.8.7
  
 VB