| Plan Review Notes For Permit 13040322 |
| Permit Number |
13040322 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-06 15:28:22 | 5-6-13 | | | | | | CONDUCTORS IN NIPPLE BETWEEN METER AND MAIN CB SHOULD | | | BE 2/0 AS PER NEC 310.15.B.6 | | | | | | ELECTRICAL AND MECHANICAL DRAWINGS DO NO MATCH. IS IT 3 | | | AC'S OR 2? COORDINATE WITH MECHANICAL | | | CONTRACTOR/ENGINEER FOR CORRECT AMOUNT AND CORRECT | | | BREAKER SIZES. CHECK AC SCHEDULE AND MATCH WITH PANEL | | | SCHEDULE. | | | | | | ANY RECEPT WITHIN 6 FEET OF BAR SINK MUST BE GFI. THERE | | | ARE NO EXCEPTIONS LISTED FOR THIS FOR BEHIND EQUIPMENT. | | | NEC 210.8.7 | | | | | | VB |
|