Plan Review Notes
Plan Review Notes For Permit 13040322
Permit Number 13040322
Review Stop B
Sequence Number 1
Notes
Date Text
2013-05-13 16:57:312010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A SURFACE WATER DRAINAGE PLAN
 THAT SHOWS COMPLIANCE WITH FBCR 401.3.
  
 2) SUBMIT 2 SETS OF SIGNED AND SEALED SUBSURFACE SOIL
 REPORTS. FBCR 401.4
  
 3) FBCR 302.1 REQUIRES EXTERIOR WALLS LOCATED ON A ZERO
 LOT LINE TO HAVE A FIRE RESISTANCE RATING OF ONE HOUR.
 SUBMIT TESTING REPORTS AND SPECIFICATIONS SHOWING THAT
 THE GLASS BLOCK PANEL WALL SYSTEM THAT IS PROPOSED FOR
 THIS WALL HAS A ONE HOUR FIRE RESISTANCE RATING IN
 ACCORDANCE WITH ASTM E 119 OR UL 263 WITH EXPOSURE FROM
 BOTH SIDES.
  
 4) THE VALUE OF $ 193,760.00 APPEARS TO BE
 UNDER-ESTIMATED FOR THIS PROJECT. PER CITY AMENDMENTS
 109.3, FOR PERMITTING PURPOSES THE VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. THE VALUE WILL BE CHANGED TO
 $412683.00 BASED ON LATEST ICC BUILDING VALUATION DATA.
  
 5) SUBMIT TWO COPIES OF THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND LISTING INFORMATION FOR THE OUTDOOR
 BBQ. FBCR M1901.2 & FBCR G2408.1
  
 6) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 ONE HOUR FIRE-RATED GLASS BLOCK, THE PRE-CAST LINTELS
 AND THE SIMPSON MBHU GIRDER TRUSS HANGER AS REQUIRED BY
 DCA RULE 9N-3.
  
 7) THE DESIGNER OF RECORD IS REQUIRED TO REVIEW AND
 APPROVE THE PRODUCT APPROVALS IN WRITING. CITY
 AMENDMENT 107.3.4.1
  
 8) SPECIFY THE EMBED DEPTH / LENGTH OF THE 3/4"
 DIAMETER ANCHOR BOLTS FOR THE DOUBLE 2 X 10 LEDGER AND
 THE THREE MEMBER GIRDER SHOWN IN DETAIL 2 ON S-2. CITY
 AMENDMENTS 107.2.1
  
 9) THE ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS HAVE THE WRONG ORIENTATION. THE FRONT DOOR
 OF THE STRUCTURE FACES EAST NOT SOUTHWEST AS SHOWN IN
 THE CALCULATIONS. PLEASE REVISE. FBC ENERGY 405.4 AND
 CITY AMENDMENTS 107.2.1
  
 10) THE UPLIFT PRESSURES FOR THE ROOF LISTED ON THE
 COVER SHEET ARE TOO LOW FOR A TWO STORY STRUCTURE
 LOCATED IN EXPOSURE CATEGORY C WITH A 170 MPH ULTIMATE/
 132 MPH ASD WINDSPEED. PLEASE REVISE. FBC R301.2.1
  
 11) THE ARCHITECTURAL AND ELECTRICAL DRAWINGS SHOW
 THREE (3) A/C SYSTEMS AND THE MECHANICAL PLANS SHOW TWO
 (2). PLEASE COORDINATE THE DRAWINGS. CITY AMENDMENTS
 107.2.1
  
 NOTE: WHEN RESUBMITTING PLEASE PROVIDE A RESPONSE
 LETTER INDICATING HOW EACH OF THE REVIEW COMMENTS HAS
 BEEN ADDRESSED.
  
  
 TRUSS DRAWING REVIEW DENIED BY BUILDING
  
 1) THE ORIGINAL WET SIGNATURE OF THE TRUSS ENGINEER AS
 WELL AS HIS SEAL IS REQUIRED ON THE TRUSS LAYOUT AND
 THE TRUSS DRAWINGS PER FS 471.025 AND FAC 61G15-23.002.
  
 2) THE STRUCTURAL DESIGNER OF RECORD IS REQUIRED TO
 REVIEW AND APPROVE THE TRUSS DRAWINGS AND LAYOUT.
 61G15-31.003
  
 3) PLEASE REVIEW TRUSS CONNECTORS FOR ADEQUATE UPLIFT
 VALUES. CITY AMENDMENTS 107.2.1 AND FBC R802.1.6.5
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW