Plan Review Notes
Plan Review Notes For Permit 13040321
Permit Number 13040321
Review Stop B
Sequence Number 2
Notes
Date Text
2013-04-30 14:05:06****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. PROJECTIONS BETWEEN 2-3' FROM THE PROPERTY LINE
 REQUIRE A 1 HOUR FIRE RATING, FBC RESIDENTIAL 2010
 TABLE 302.1. ROOF PANELS ARE SHOWN 2' FROM PROPERTY
 LINE.
  
 2ND REVIEW, NOT ADDRESSED.
  
 ALSO NOTE THAT THE TWO SITE PLANS ARE NOT THE SAME. ONE
 SHOWS A 2' SETBACK FROM PROPERTY LINE, THE OTHER SHOWS
 NONE. A 12" OVERHANG IS SHOWN ON THE PLAN, SO THE
 PROPOSED PLANS SHOW EITHER A ROOF WHICH IS 2' FROM
 PROPERTY LINE OR EXTENDING OVER THE PROPERTY LINE (NOT
 PERMITTED). FIRE RSISTANCE IS REQUIRED IN EITHER CASE.
  
 2. PROVIDE TWO SETS OF THE FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL FOR THE ROOF PANELS FAC9N-3. IF USING
 A FLORIDA STATE PRODUCT APPROVAL, INCLUDE COVER SHEET
 (WHICH SHOWS APPROVAL NUMBER), EVALUATION REPORT, AND
 INSTALLATION INSTRUCTIONS.
  
 2ND REVIEW, NOT ADDRESSED.
  
 A DOCUMENT WHICH APPEARS TO BE A PART OF A NOA WAS
 SUBMITTED. PROVIDE COMPLETE NOA OR FLORIDA STATE OR
 LOCAL PRODUCT APPROVAL (COVER SHEET, EVALUATION REPORT,
 INSTALLATION INSTRUCTIONS).
  
 NEW COMMENT:
  
 3. ONLY ONE DRAWING FOR THE ROOF PANELS WAS SUBMITTED.
 TWO COMPLETE, IDENTICAL SETS OF PLANS REQUIRED FOR
 PERMIT ISSUANCE.
  
  