Plan Review Notes
Plan Review Notes For Permit 13040312
Permit Number 13040312
Review Stop E
Sequence Number 1
Notes
Date Text
2013-04-15 10:41:49THE ELECTRICAL SERVICE MAINS MUST BE GROUPED IN ONE
 LOCATION. THE PRINCIPAL SAFETY RULE FOR ELECTRICAL
 SERVICES REQUIRES A BUILDING OR STRUCTURE TO HAVE ONE
 POINT OF SERVICE. NEC 230.2, 230.71, 230.72
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRICAL SERVICE AND SWITCH GEAR. NEC 110.9, 110.10
  
 PROVIDE PROPER DOWNSTREAM RATINGS OF EQUIPMENT IN
 ACCORDANCE WITH THE FAULT CURRENT AND/OR PROVIDE PROPER
 SERIES RATINGS VALUES 240.4 (B) (C) (F), 240.12
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 GROUND FAULT PROTECTION EQUIPMENT (GFPE) IS REQUIRED
 FOR THE NEW ELECTRIC SERVICE. NEC 230.95, 240.13
  
 PROVIDE AND ILLUSTRATE THE SAFE WORKING CLEARANCES AND
 DEDICATED WORKING SPACE AT ALL ELECTRICAL PANEL BOARDS
 AND TRANSFORMERS. NEC 110.26, 240.24
  
 EQUIPMENT GROUNDING CONDUCTORS IN PARALLEL TO BE FULL
 SIZED 250.122 (F)
  
 HOW WILL EXISTING LIGHTING, 120V AND 240V EQUIPMENT BE
 MAINTAINED? PLAN INDICATES THIS EQUIPMENT IS TO REFED
 ?IN FUTURE? AND NOT AT THIS TIME.
  
 REVIEW INCOMPLETE BASED ON MISSING INFORMATION
  