| 2013-04-27 17:42:15 | 2901 TUXEDO AVENUE |
| | PERMIT #13040308 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NOTE: THIS IS A STATE FACILITY; THEREFORE, THE FLORIDA |
| | STATE FIRE MARSHAL'S OFFICE HAS JURISDICTION AND IS |
| | RESPONSIBLE FOR PLAN APPROVAL AND FIRE INSPECTIONS. WPB |
| | FIRE RESCUE WILL PERFORM A COURTESY FIRE PLAN REVIEW |
| | ONLY: |
| | |
| | ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101 REFER TO |
| | NFPA 101-THE LIFE SAFETY CODE (2009 EDITION WITH |
| | FLORIDA AMENDMENTS.) |
| | |
| | SHEET LS1.01: UPDATE THE CODE LIST TO REFERENCE THE |
| | 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH |
| | CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 |
| | WITH FLORIDA AMENDMENTS. |
| | |
| | GENERAL: PROVIDE DRAWING NOTE INDICATING ALL |
| | CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE |
| | REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS |
| | SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | GENERAL: PROVIDE DRAWING NOTE INDICATING, ?FIRE |
| | PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND |
| | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| | 500 NORTH DIXIE HIGHWAY.? |
| | |
| | GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | GENERAL: PROVIDE BUILDING ADDRESS VISIBLE FROM THE |
| | STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING AND |
| | BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND |
| | SHALL CONTRAST THE BACKGROUND. |
| | |
| | GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| | DOORS WITH EXIT SIGNS. |
| | |
| | GENERAL: PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL |
| | BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING |
| | READING FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | SHEET LS1.01: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING |
| | FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM |
| | POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM |
| | THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE |
| | NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | SHEET LS1.01 & A7.01: FOR ASSEMBLY OCCUPANCIES WITH AN |
| | OCCUPANT LOAD OF 50 OR MORE PERSONS, PANIC/FIRE EXIT |
| | HARDWARE SHALL BE PROVIDED ON DOORS TO RELEASE THE |
| | LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE PERMITTED |
| | THAT WOULD NOT BE RELEASED BY THE PANIC/FIRE EXIT |
| | HARDWARE. CLEARLY INDICATE ALL DOORS TO BE EQUIPPED |
| | WITH PANIC OR FIRE EXIT HARDWARE. |
| | |
| | SHEET E4.01: PER SECTION 13.3.4.3.3, PROVIDE |
| | SPEAKER/STROBE NOTIFICATION APPLIANCES AS ASSEMBLY |
| | OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 300 |
| | OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY |
| | VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS. |
| | |
| | REHABILITATION: PER SECTION 43.6.4.1, IN A BUILDING |
| | WITH REHABILITATION WORK AREAS INVOLVING OVER 50 |
| | PERCENT OF THE AGGREGATE BUILDING AREA, AUTOMATIC |
| | SPRINKLER SYSTEMS SHALL BE PROVIDED ON THE HIGHEST |
| | FLOOR CONTAINING A REHABILITATION WORK AREA AND ON ALL |
| | FLOORS BELOW IN ACCORDANCE WITH THE REQUIREMENTS OF |
| | OTHER SECTIONS OF THIS CODE APPLICABLE TO NEW |
| | CONSTRUCTION FOR THE OCCUPANCY. PER SECTION 12.3.5.2 |
| | (NEW ASSEMBLY OCCUPANCY), ANY BUILDING CONTAINING ONE |
| | OR MORE ASSEMBLY OCCUPANCIES WHERE THE AGGREGATE |
| | OCCUPANT LOAD OF THE ASSEMBLY OCCUPANCIES EXCEEDS 300 |
| | SHALL BE PROTECTED BY AN APPROVED, SUPERVISED AUTOMATIC |
| | SPRINKLER SYSTEM. PER SECTION 43.8.1.2, AN ADDITION |
| | SHALL NOT CREATE OR EXTEND ANY NONCONFORMITY WITH |
| | REGARD TO FIRE SAFETY OR THE MEANS OF EGRESS IN THE |
| | EXISTING BUILDING FOR WHICH THE ADDITION IS |
| | CONSTRUCTED. |
| | |
| | FIRE SPRINKLERS: FOR ISSUANCE OF A GENERAL BUILDING |
| | PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING |
| | CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION |
| | DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE |
| | AUTOMATIC FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE |
| | CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| | DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| | WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |
| | NOTE: SEPARATE SHOP DRAWINGS AND SUB-PERMITS NEEDED FOR |
| | FIRE ALARM, FIRE SPRINKLER, KITCHEN HOOD AND KITCHEN |
| | HOOD SUPPRESSION SYSTEM. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |