| Plan Review Notes For Permit 13040308 |
| Permit Number |
13040308 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-07 10:23:50 | SHEET E3.01 ? EXHAUST FAN TO REMAIN RUNNING UPON ANSUL | | | ACTIVATION | | | E6.01 GENERATOR REQUIRES EQUIPMENT GROUNDING CONDUCTOR, | | | CONNECTED AFTER MAIN DISCONNECT AND INDICATION OF | | | GENERATOR SIZE AND OCP | | | PROVIDE AIC RATING OF SECOND 800A MAIN AT MDP | | | FEEDER SCHEDULE CHART SHOWS EGC SPLIT FOR PARALLEL. EGC | | | TO BE FULL SIZE PER 250.122 (F) | | | PLEASE PROVIDE INFORMATION REGARDING TRANSFER AND | | | TRANSFER SWITCH AS TO IF MAIN AND TRANSFER ARE ONE | | | PIECE OF GEAR AND RATED FOR SERVICE ENTRANCE, HOW | | | TRANSFER IS ACCOMPLISHED, 3 POLE OR 4 POLE, NEUTRALS | | | AND GROUNDS ARE TO BE SEPARATED AFTER THE FIRST MEANS | | | OF DISCONNECT. PLANS DO APPEAR CLEAR FOR THIS | | | INFORMATION. | | | PROVIDE AIC RATING OF CT CAN AND COORDINATE WITH | | | SYSTEM. | | | PROVIDE ENERGY CODE COMPLIANCE STATEMENT AND ENERGY | | | BUDGET CALCULATIONS | | | |
|