| 2013-04-23 13:03:55 | BUILDING PLAN REVIEW |
| | PERMIT: 13040308 |
| | ADD: 2901 TUXEDO AVENUE |
| | CONT: WEST CONSTRUCTION |
| | TEL: (561)588-2027 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1 ST REVIEW |
| | DATE: APRIL 23/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1.00: |
| | 1A ) UNDER THE HEADING OF SITE CODE COMPLIANCE THE |
| | PLANS INDICATE 13 NEW PARKING SPACES BUT THERE IS A |
| | TOTAL OF 85 PARKING SPACES THAT WILL REQUIRE 4 |
| | ACCESSIBLE PARKING SPACES SEE THE 2010 FL ACCESSIBILITY |
| | CODE TABLE 208.2. |
| | |
| | 1B) THE PLANS ALSO SHOW THE 2 ACCESSIBLE PARKING SPACES |
| | GROUPED TOGETHER. THE 2010 FL ACCESSIBILITY CODE |
| | SECTION 208.3.1 WHEN PARKING SERVES MORE THAN ONE |
| | ACCESSIBLE ENTRANCE, PARKING SPACES COMPLYING WITH 502 |
| | SHALL BE DISPERSED AND ON THE SHORTEST ACCESSIBLE ROUTE |
| | TO THE ACCESSIBLE ENTRANCE. |
| | |
| | 1C) THE NEW PARKING SPACES SHOWN TO THE NORTH OF THE |
| | BUILDING ARE DOUBLE STRIPED TO THE CITY ZONING STANDARD |
| | BUT THE PARKING TO THE WEST OF THE BUILDING ARE SINGLE |
| | STRIPED AND ARE BEING RE-STRIPED. THEY WILL NEED TO BE |
| | DOUBLE STRIPED TO MEET THE CITY ZONING STANDARDS. |
| | |
| | 1D) JUST A NOTE OF CAUTION ON THE REDESIGN, 2010 FL |
| | ACCESSIBILITY CODE 208.3.1 ALL SPACES MUST BE LOCATED |
| | ON AN ACCESSIBLE ROUTE THAT IS 44 INCHES WIDE AND SO |
| | THAT USERS ARE NOT COMPELLED TO WALK OR WHEEL BEHIND |
| | VEHICLES EXCEPT BEHIND HIS OR HER OWN VEHICLE. |
| | |
| | 1E) THIS BUILDING IS LOCATED IN A FLOOD ZONE, A-9 AND |
| | WILL NEED FLOOD ZONE CERTIFICATES: |
| | 1) BEFORE THE ISSUANCE OF THE PERMIT WITH PROPOSED |
| | ELEVATION OF FINISHED SLAB IN |
| | NGVD. |
| | 2) ONCE THE FLOOR SLAB HAS BEEN POURED AND FINISHED. |
| | 3) BEFORE THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY, |
| | OR CERTIFICATE OF |
| | COMPLETION. |
| | FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES |
| | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | |
| | FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| | JULY 31,2015 |
| | |
| | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| | USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015. |
| | THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL |
| | SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE |
| | FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING |
| | COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS |
| | CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED |
| | ON THE NEW FORM. |
| | |
| | ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW |
| | FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 2) SHEET LS1.01: |
| | 2A) NEW SUPPLY AND STORAGE ROOM # 116 AND OFFICE # 114, |
| | MISSING OCCUPANCY SEPARATION BETWEEN THESE OCCUPANCIES. |
| | THIS STORAGE AREA IS LARGER THAN 10 % OF THE BUILDING |
| | FOOTPRINT NO LONGER BEING CLASSIFIED AS A ACCESSORY |
| | OCCUPANCY. FBC-B 508.2.1. |
| | |
| | 2B) THE NEW MECHANICAL ROOM # 129 AND STORAGE ROOMS TO |
| | THE EAST ARE MISSING THE OCCUPANCY SEPARATION WALL |
| | CLASSIFICATION WITH THE ASSEMBLY OCCUPANCY, FBC-B TABLE |
| | 508.4. |
| | |
| | 2C) THE NEW MECHANICAL ROOM # 123 INDICATES 2 OF THE |
| | WALLS WITH A OCCUPANCY SEPARATION RATING BUT MISSING |
| | THE OTHER 2 WALLS, FBC-B TABLE 508.2.5. |
| | |
| | 2D) SHEET A.101 WALL TAGS IDENTIFYING WALL TYPE DO NOT |
| | INDICATE RATED WALL OCCUPANCY SEPARATION AS SHOWN ON |
| | THE LS PLAN. WALLS TYPES LOCATED ON SHEET A5.01 DOORS |
| | ON A7.01. |
| | |
| | 3) SHEET A5.02 |
| | 3A) DETAIL # 5 NEW RAMP, PLEASE SEE HANDRAIL HEIGHT AT |
| | STAIR, 2010 FL ACCESSIBILITY CODE 505.4 HANDRAIL HEIGHT |
| | BETWEEN 34?-38?. |
| | |
| | 3B) DETAIL # 5 ALSO IS MISSING THE HANDRAIL EXTENSIONS |
| | REQUIRED BY FL ACCESSIBILITY CODE 505.10. |
| | |
| | 3C) DETAIL #9 THE WALL MOUNTED DETAIL INDICATES THE |
| | MINIMUM DISTANCE FROM THE WALL IS 2 ? INCHES PLEASE |
| | REVIEW 2010 FL ACCESSIBILITY CODE 505.5 CLEARANCE. |
| | |
| | 3D) DETAIL # 6 & 8 THE BOTTOM LANDING IS NOT |
| | DIMENSIONED BUT SCALES OUT LESS THAN 5?-0? IN LENGTH ( |
| | DIRECTION OF TRAVEL) SEE FL ACCESSIBILITY CODE 405.7.3. |
| | |
| | 4A) SHEET A4.01, A4.02 & A5.04 BRICK WALL DETAILS 1 & |
| | 2, PLEASE REVIEW 2010 FBC-B SECTION 2114.2 CONCRETE |
| | BEARING LEDGE. BRICK, STONE OR OTHER VENEER SHALL BE |
| | SUPPORTED BY A CONCRETE BEARING LEDGE AT LEAST EQUAL TO |
| | THE TOTAL THICKNESS OF THE BRICK, STONE OR OTHER |
| | VENEER, WHICH IS POURED INTEGRALLY WITH THE CONCRETE |
| | FOUNDATION. NO SUPPLEMENTAL CONCRETE FOUNDATION POURS |
| | WHICH WILL CREATE A HIDDEN COLD JOINT SHALL BE USED |
| | WITHOUT SUPPLEMENTAL TREATMENT IN THE FOUNDATION UNLESS |
| | THERE IS AN APPROVED PHYSICAL BARRIER. AN APPROVED |
| | PHYSICAL BARRIER SHALL ALSO BE INSTALLED FROM BELOW THE |
| | WALL SILL PLATE OR FIRST BLOCK COURSE HORIZONTALLY TO |
| | EMBED IN A MORTAR JOINT. IF MASONRY VENEER EXTENDS |
| | BELOW GRADE, A TERMITE PROTECTIVE TREATMENT MUST BE |
| | APPLIED TO THE CAVITY CREATED BETWEEN THE VENEER AND |
| | THE FOUNDATION, IN LIEU OF A PHYSICAL BARRIER. |
| | |
| | EXCEPTION: VENEER SUPPORTED BY A SHELF, ANGLE OR LINTEL |
| | SECURED TO THE FOUNDATION SIDEWALL IN ACCORDANCE WITH |
| | TMS 402/ACI 530/ASCE 5, PROVIDED AT LEAST A 6-INCH (152 |
| | MM) CLEAR INSPECTION SPACE OF THE FOUNDATION SIDEWALL |
| | EXTERIOR EXISTS BETWEEN THE VENEER AND THE TOP OF ANY |
| | SOIL, SOD, MULCH OR OTHER ORGANIC LANDSCAPING |
| | COMPONENT, DECK, APRON, PORCH, WALK OR ANY OTHER WORK |
| | IMMEDIATELY ADJACENT TO OR ADJOINING THE STRUCTURE. |
| | |
| | 4B) PLANS DO NOT INDICATE HOW THE BRICK VENEER WILL BE |
| | ATTACHED TO THE CMU WALL, PROVIDE COMPLIANCE WITH 2010 |
| | FBC-B 1405.6 ANCHORED MASONRY VENEER. |
| | |
| | 5) COMPLIED SEE SHEET G0.01 FOR APPROVAL OF COMPONENTS |
| | & CLADDING PRODUCT APPROVALS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |