| Plan Review Notes For Permit 13040307 |
| Permit Number |
13040307 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-06 15:42:56 | 5-06-13 | | | | | | 1. CONDUCTORS IN NIPPLE BETWEEN METER AND 200A MCB | | | SHOULD BE 2/0 PER 310.15.B.6 | | | 2. COORDINATE ELECTRICL PANEL SCHEDULE WITH AC | | | EQUIPMENT SCHEDULE. NOTHING MATCHES, INSTALL CORRECT | | | BREAKERS | | | 3. ANY RECEPT WITHIN 6 FT OF WET SINK MUST BE GFI PER | | | NEC 210.8.7. THERE ARE NO EXCEPTIONS LISTED. | | | VB |
|