| 2013-04-19 11:20:31 | BUILDING PLAN REVIEW |
| | PERMIT: 13040277 |
| | ADD: 1801 S FLAGLER # 1711 |
| | CONT: FREDRICK BLACK & ASSOCIATES |
| | TEL: (561)547-4772 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | REVIEW |
| | DATE: |
| | ACTION: BUILDING PROVISO: |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) SHEET 1 UNDER THE HEADING FINISHES: REPLACE CERAMIC |
| | TILE IN BATHROOMS AND LAMINATED PARQUET ALL OTHER |
| | AREAS. "EASY MAT" SOUND PROOFING UNDERLAYMENT ECB75. |
| | NO PRODUCT DATA WAS SUBMITTED PROVIDING COMPLIANCE WITH |
| | THE LISTED CODE SECTIONS; |
| | 2010 FBC-B 603.2 |
| | 1A) (CERAMIC TILE ) (1). INSULATION PLACED BETWEEN TWO |
| | LAYERS OF NONCOMBUSTIBLE MATERIALS WITHOUT AN |
| | INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME |
| | SPREAD INDEX OF NOT MORE THAN 100. |
| | |
| | 1B) (WOOD PARQUET FLOORING) (2) INSULATION INSTALLED |
| | BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT |
| | INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME |
| | SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | 2) 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 3) DOCUMENTS WILL NEED TO BE SUBMITTED TO THE DESIGNER |
| | OF RECORD FOR SHOP DRAWING STAMP REVIEW BEFORE |
| | SUBMITTAL TO THE BUILDING DEPARTMENT. FL 61G1-23.015 |
| | (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND |
| | REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS |
| | ETC... |
| | |
| | DOCUMENTS WILL NEED TO BE IN AND APPROVED BY THE |
| | BUILDING DEPARTMENT BEFORE FRAMING INSPECTION APPROVAL. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |