| Plan Review Notes For Permit 13040273 |
| Permit Number |
13040273 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2013-06-28 14:45:48 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- RAS 117 CALCULATIONS FOR FLAT ROOF: A) ENGINEER TO | | | REVIEW SEC. 8.1 OF RAS 117 AND REVISE NAILING FOR FIELD | | | ZONE #1. B) PROVIDE COMPLETE LAP & FIELD NAILING | | | SPECIFICATIONS FOR PERIMETER AND CORNER AREAS. C) | | | ENGINEER TO USE CURRENT ENGINEER SEAL. | | | 2- REVISE ENERGY CALCULATIONS AND PLANS TO MATCH: | | | A)PROVIDE SPECIFICATIONS/DETAILS SHOWING HOW THE ATTIC | | | AND CEILING ARE VENTED. INCLUDING THE NEW ADDITION. B) | | | DOORS ON SHEET 3 OF 6. REVISE ORIENTATION TO MATCH | | | PLANS. | | | 3- REVISE EXTERIOR WALL SECTION ON SHEET S.2. THERE IS | | | NO TILE ROOF ON THIS PROJECT. | | | 4- REVISE CRAWL SPACE VENTILATION INFORMATION (SEE SEC. | | | R408): A) MIN. NET AREA SHALL NOT BE LESS THAN 1S.F. | | | PER 150S.F. (16"X8" DOESN'T COMPLY). B)SHOW LOCATION OF | | | THE 3 VENTILATION OPENINGS. C) ACCESS PANEL SIZE SHOWN | | | DOESN'T COMPLY WITH SEC. R408.4. D) NEED PANEL LOCATION | | | WITHIN 3'-0" OF EACH CORNER. |
|