2013-06-28 14:45:48BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- RAS 117 CALCULATIONS FOR FLAT ROOF: A) ENGINEER TO
 REVIEW SEC. 8.1 OF RAS 117 AND REVISE NAILING FOR FIELD
 ZONE #1. B) PROVIDE COMPLETE LAP & FIELD NAILING
 SPECIFICATIONS FOR PERIMETER AND CORNER AREAS. C)
 ENGINEER TO USE CURRENT ENGINEER SEAL.
 2- REVISE ENERGY CALCULATIONS AND PLANS TO MATCH:
 A)PROVIDE SPECIFICATIONS/DETAILS SHOWING HOW THE ATTIC
 AND CEILING ARE VENTED. INCLUDING THE NEW ADDITION. B)
 DOORS ON SHEET 3 OF 6. REVISE ORIENTATION TO MATCH
 PLANS.
 3- REVISE EXTERIOR WALL SECTION ON SHEET S.2. THERE IS
 NO TILE ROOF ON THIS PROJECT.
 4- REVISE CRAWL SPACE VENTILATION INFORMATION (SEE SEC.
 R408): A) MIN. NET AREA SHALL NOT BE LESS THAN 1S.F.
 PER 150S.F. (16"X8" DOESN'T COMPLY). B)SHOW LOCATION OF
 THE 3 VENTILATION OPENINGS. C) ACCESS PANEL SIZE SHOWN
 DOESN'T COMPLY WITH SEC. R408.4. D) NEED PANEL LOCATION
 WITHIN 3'-0" OF EACH CORNER.