| 2013-05-29 15:45:26 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND |
| | CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- ENGINEER TO USE CURRENT ENGINEER SEAL AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTES. NEW SEAL SAYS "LICENSE" |
| | NOT "CERTIFICATE" . PROVIDE NEW DRAWINGS WITH CURRENT |
| | SEAL. |
| | |
| | 2- ACCORDING TO SEC. R301.2.1.4.3 OF 2010 |
| | FBC-RESIDENTIAL, THIS BUILDING IS LOCATED ON EXPOSURE |
| | "C". |
| | A) THE DESIGN PRESSURES SPECIFIED ON THE WINDOW |
| | SCHEDULE ARE STILL TOO LOW FOR EXPOSURE "C" ON WINDOWS |
| | LOCATED IN THE WALL ZONE 5. REVISE AS REQUIRED. |
| | ***NOTE: SOME WINDOWS ARE LOCATED ON ZONE 5. SEE NOTE |
| | "A" ON FIGURE R301.2(7) OF 2010 FBC-RESIDENTIAL FOR |
| | MINIMUM "A" DIMENSION REQUIRED. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) SIMPSON STRUCTURAL CONNECTORS CBSQ-SDS2. INFORMATION |
| | SUBMITTED ER-5952 IS NOT AN APPROVED FLORIDA PRODUCT |
| | APPROVAL. IF THERE IS NOT CURRENT PRODUCT APPROVAL, |
| | THEN MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL. |
| | |
| | B) FLAT ROOF: (1) ENGINEER TO REVIEW SEC. 8.1 OF RAS |
| | 117 AND REVISE NAILING FOR FIELD ZONE #3 AS REQUIRED. |
| | (2) ENGINEER TO SPECIFY NAIL SPACING FOR THE LAP AND |
| | NUMBER OF ROWS AND SPACING FOR THE FIELD STAGGERED ROWS |
| | FOR PERIMETER AND CORNER AREAS. (3) ENGINEER TO USE |
| | CURRENT ENGINEER SEAL AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTE. |
| | |
| | 4- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE |
| | DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT |
| | FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 5- REVISE AND PROVIDE COMPLETE ENERGY CALCULATIONS |
| | SUBMITTED (SEC. 107.2.1 CITY AMENDMENTS TO FBC): |
| | A) THE AREA WEIGHTED AVERAGE OVERHANG DEPTH OF 7.720 FT |
| | ON ITEM #7 IS INCORRECT. TYPICAL OVERHANG ON THIS HOUSE |
| | IS 6" OR LESS. SEE EXTERIOR ELEVATIONS AND REVISE AS |
| | REQUIRED. |
| | ***NOTE: REVISE ALL THE WINDOWS WALL ORIENTATION, |
| | OVERHANG DEPTH AND SEPARATION, SQUARE FOOTAGE AND |
| | NUMBER OF WINDOWS/DOORS WITH GLAZING TO MATCH PLANS. |
| | |
| | B) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS ON PLANS |
| | SHOWING HOW THE HOUSE COMPLIES WITH THE "CF" AND "CV" |
| | CREDITS TAKEN ON ITEM #15. |
| | ***NOTE: SEE TABLE 405.6.6 AND SEC. 405.6.4 OF 2010 |
| | FBC-ENERGY CONSERVATION. AND REVISE CALCULATIONS AND |
| | PLANS AS REQUIRED. |
| | |
| | C) PROVIDE SPECIFICATIONS/DETAILS SHOWING HOW THE ATTIC |
| | AND CEILING ARE VENTED AS SPECIFIED ON SHEET 2 OF 6 |
| | SUBMITTED. (COORDINATE WITH PLANS). |
| | ***NOTE: EXTERIOR ELEVATIONS ONLY SHOW ONE GABLE VENT |
| | ON SOUTH ELEVATION. THIS DOESN'T PROVIDE CROSS |
| | VENTILATION. ALSO, COORDINATE THIS ITEM WITH THE CROSS |
| | VENTILATION CREDIT TAKEN ON ITEM # 5(B) ABOVE. |
| | |
| | D) DOORS ITEM ON SHEET 3 OF 6: CLARIFY THE DOOR |
| | ORIENTATION. LOOK AT NORTH ARROW ON PLANS FOR CORRECT |
| | ORIENTATION. REVISE AS REQUIRED. |
| | |
| | 6- ACCORDING TO PLANS SUBMITTED THE ROOF PITCH IS 3/12. |
| | NEED TO SPECIFY TWO LAYERS OF UNDERLAYMENT AS REQUIRED |
| | BY SEC. R905.2.2 OF 2010 FBC-RESIDENTIAL. |
| | ***NOTE: REVISED NOTE SPECIFY 2 LAYERS OF PLYWOOD |
| | INSTEAD OF 2 LAYERS OF UNDERLAYMENT. REVISE AS |
| | REQUIRED. |
| | |
| | 7- PROVIDE COMPLETE DETAILS, SPECIFICATION AND LOCATION |
| | OF THE CROSS VENTILATION AND ACCESS OF THE CRAWL SPACE |
| | AS REQUIRED BY SEC. R408 OF 2010 FBC-RESIDENTIAL. |
| | ***NOTE: INFORMATION SUBMITTED DOESN'T COMPLY. READ |
| | CITED SECTION AND REVISE AS REQUIRED. |
| | |
| | 8- NEED TO SPECIFY GUTTERS WITH DOWNSPOUTS AS REQUIRED |
| | BY SEC. R318.6 OF 2010 FBC-RESIDENTIAL. |
| | ***NOTE: INFORMATION SUBMITTED ON SHEET S.2 IS |
| | INCOMPLETE. MISSING GUTTERS SIZE. 2" DIAMETER DOWNSPOUT |
| | IS TOO SMALL. PROVIDE GUTTER AND DOWNSPOUT SIZING |
| | CALCULATIONS. |
| | |
| | 9- PROVIDE COMPLETE DETAILS AND SPECIFICATION SHOWING |
| | COMPLIANCE WITH THE ROOF VENTILATION AS REQUIRED BY |
| | SEC. R806 OF 2010 FBC-RESIDENTIAL. |
| | ***NOTE: INFORMATION SUBMITTED DOESN'T COMPLY WITH |
| | CROSS VENTILATION. AND, COORDINATE WITH CREDIT TAKEN ON |
| | THE ENERGY CALCULATIONS. |
| | |
| | 10- SHEET S.4: |
| | A) REVISE GENERAL ROOF NOTES #8. NEED TO USE 8D RING |
| | SHANK NAILS ONLY. SEC. R803.2.3.1 OF 2010 |
| | FBC-RESIDENTIAL. REVISE NOTE AS REQUIRED. |
| | |