2013-04-23 17:00:11RESIDENTIAL (R3) ADDITION, PLUMBING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE PLUMBING RISER DIAGRAM. THE WASHER NEEDS TO
 DISCHARGE DOWNSTREAM OF THE BATHROOM GROUP. AND, THE
 BATHROOM GROUP DRY VENT IS NOT PROPERLY LOCATED. SEC.
 P3108 OF 2010 FBC-RESIDENTIAL.
  
 ***NOTE: YOU MAY CONTACT THE LICENSED PLUMBER DOING THE
 JOB TO SEE HOW HE/SHE PROPOSES TO VENT THE BATHROOM
 GROUP ACCORDING TO THE PROPOSED BATHROOM LAYOUT. THIS
 WILL ELIMINATE ANY DISCREPANCIES OR DELAYS IN THE
 FIELD.
  