| Plan Review Notes For Permit 13040270 |
| Permit Number |
13040270 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-04-12 16:55:17 | RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- MECHANICAL PLAN WAS NOT REVISED BY THE ARCHITECT OF | | | RECORD. ONLY THE GAS RISER WAS REVISED. ARCHITECT NEED | | | TO REVISE THE MECHANICAL PLAN AND AND AND SEAL AS | | | REQUIRED BY SEC. 107.1 CITY AMENDMENTS TO FBC. | | | | | | 2- ELECTRICAL PLAN SUBMITTED WITH A/C REDLINES: | | | A) REVISE MECHANICAL PLAN. REDLINES ON ELECTRICAL PLAN | | | IS NOT ACCEPTABLE. SEE ITEM #1 ABOVE. | | | | | | B) THE 5 TON A/C CONDENSER UNIT SHOWS A RETURN GRILL ON | | | THE WALL BETWEEN THE KITCHEN AND THE CLOSET. THIS | | | LOCATION IS NOT ALLOWED BY SEC. M1602.2. REVISE | | | MECHANICAL PLAN AS REQUIRED. SEE ITEM #1 ABOVE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|