| 2013-05-02 09:41:52 | 4847 FRED GLADSTONE DRIVE |
| | TRACKING #13040209 |
| | PERMIT #12100269 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | *****APPROVED W/ PROVISIONS - SUBMIT REVISION***** |
| | |
| | SHEET G101: EXIT DOOR #106 (LOCATED IN DAY ROOM 4 - |
| | #106) APPEARS TO BE EQUIPPED WITH A MAGNETIC LOCK AND |
| | CARD READER. PER SECTION 7.2.1.6.2 OF NFPA 101 FLORIDA |
| | EDITION 2009 ALLOWS ACCESS CONTROLLED EGRESS DOORS |
| | PROVIDED THAT ALL SEVEN OF THE FOLLOWING CRITERIA ARE |
| | MET: |
| | 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE, |
| | ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT |
| | ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON |
| | DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER |
| | TO THE SENSOR. |
| | 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL |
| | SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK |
| | THE DOORS IN THE DIRECTION OF EGRESS. |
| | 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE |
| | DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE |
| | LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND |
| | WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS. |
| | 4. THE MANUAL RELEASE DEVICE SHALL BE READILY |
| | ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS |
| | PUSH TO EXIT. |
| | 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL |
| | RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK, |
| | INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS, |
| | AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN |
| | 30 SECONDS. |
| | 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL |
| | AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF |
| | EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE |
| | FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. |
| | 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER |
| | SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL |
| | AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF |
| | EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE |
| | FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. |
| | |
| | SHEET E301: THREE EXIT SIGNS MISSING FROM PLAN. REFER |
| | TO SHEET G101 FOR COORDINATION. |
| | |
| | SHEET E401: FLOOR PLAN IS NOT THE SAME AS THE |
| | ARCHITECTURAL FLOOR PLAN OF SHEET A101. |
| | |
| | SHEET E401: NO FIRE ALARM NOTIFICATION APPLIANCES |
| | LOCATED IN DAY ROOM 3 & 4 OR IN IDT #109. FIRE ALARM |
| | ANNUNCIATOR PANEL MISSING FROM RECEPTION #102. |
| | |