| Plan Review Notes For Permit 13040205 |
| Permit Number |
13040205 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-09-04 11:52:31 | 1720 PALM BEACH LAKES BOULEVARD | | | TRACKING #13040205 | | | PERMIT #12100336 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | RESPONSE COMMENT: THE BUILDING OCCUPANT LOAD IS | | | INDICATED AS 99 PERSONS; HOWEVER, THE KITCHEN AREA | | | OCCUPANT LOAD FACTOR IS INDICATED AS 200 SQ.FT. PER | | | PERSON (PER FBC) BUT THE LIFE SAFETY CODE (NFPA 101) | | | TABLE 7.3.1.2 INDICATES THE OCCUPANT LOAD FACTOR FOR | | | KITCHENS IS TO BE FIGURED AT 100 SQ.FT. PER PERSON | | | WHICH WILL RESULT IN A BUILDING OCCUPANT LOAD OF 106 | | | PERSONS AND THEREFORE WILL STILL REQUIRE AUTOMATIC | | | SPRINKLER PROTECTION. ADDITIONALLY, THERE IS OPEN FLOOR | | | AREA ADAJACENT TO THE SEATING AND STANDING AREAS THAT | | | HAS NOT BEEN FIGURED INTO THE TOTAL POSSIBLE OCCUPANT | | | LOAD. | | | | | | ORIGINAL COMMENT - ENCLOSED ADDITION: THE 90 FIXED | | | SEATS ADDED TO THE OCCUPANT LOAD OF THE | | | STANDING/ORDERING CUSTOMERS WILL RESULT IN A NEW | | | OCCUPANT LOAD EXCEEDING 100 PERSONS. PER FBC SECTION | | | 903.2.1.2 AN AUTOMATIC SPRINKLER WILL BE REQUIRED. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|