Plan Review Notes
Plan Review Notes For Permit 13040205
Permit Number 13040205
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2013-09-04 11:52:311720 PALM BEACH LAKES BOULEVARD
 TRACKING #13040205
 PERMIT #12100336
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: THE BUILDING OCCUPANT LOAD IS
 INDICATED AS 99 PERSONS; HOWEVER, THE KITCHEN AREA
 OCCUPANT LOAD FACTOR IS INDICATED AS 200 SQ.FT. PER
 PERSON (PER FBC) BUT THE LIFE SAFETY CODE (NFPA 101)
 TABLE 7.3.1.2 INDICATES THE OCCUPANT LOAD FACTOR FOR
 KITCHENS IS TO BE FIGURED AT 100 SQ.FT. PER PERSON
 WHICH WILL RESULT IN A BUILDING OCCUPANT LOAD OF 106
 PERSONS AND THEREFORE WILL STILL REQUIRE AUTOMATIC
 SPRINKLER PROTECTION. ADDITIONALLY, THERE IS OPEN FLOOR
 AREA ADAJACENT TO THE SEATING AND STANDING AREAS THAT
 HAS NOT BEEN FIGURED INTO THE TOTAL POSSIBLE OCCUPANT
 LOAD.
  
 ORIGINAL COMMENT - ENCLOSED ADDITION: THE 90 FIXED
 SEATS ADDED TO THE OCCUPANT LOAD OF THE
 STANDING/ORDERING CUSTOMERS WILL RESULT IN A NEW
 OCCUPANT LOAD EXCEEDING 100 PERSONS. PER FBC SECTION
 903.2.1.2 AN AUTOMATIC SPRINKLER WILL BE REQUIRED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730