| 2013-09-25 08:03:49 | 2010 FBC / 2008 NEC |
| | |
| | DENIED BY ELECTRIC |
| | |
| | 1) SPECIFY ON THE PLANS WHETHER THE UNDER-GROUND |
| | SERVICE LATERAL IS UTILITY (FLORIDA POWER & LIGHT) OR |
| | CUSTOMER OWNED. IF IT IS CUSTOMER OWNED SPECIFY THE |
| | SERVICE CONDUCTOR SIZES. NEC 230.31 |
| | |
| | 2) PROVIDE TOTAL SERVICE LOAD (HOUSE LOAD) |
| | CALCULATIONS. NEC 220.84 (B) |
| | |
| | 3) SPECIFY THE SIZES OF ALL CONDUCTORS ON THE PLANS. |
| | NEC 310.15 |
| | |
| | 4) SHOW THE LOCATION OF THE HOUSE PANEL "H" ON THE |
| | PLANS. NEC ARTICLE 408 |
| | |
| | 5) SHOW LOCATION OF THE DISCONNECT/ OVER-CURRENT |
| | PROTECTION FOR THE 50 AMP HOUSE PANEL "H" ON THE PLANS. |
| | NEC 230.72, 230.91 & 240.21 |
| | |
| | 6) A 150 AMP DISCONNECT/ OVER-CURRENT PROTECTION IS |
| | SHOWN FOR THE 100 AMP PANEL "A". COMPLY WITH NEC 408.36 |
| | WHICH REQUIRES THE OVER-CURRENT PROTECTION RATING TO |
| | NOT BE MORE THAN THE PANEL. PLEASE CORRECT. |
| | |
| | 7) SHOW THE REQUIRED DISCONNECT/ OVERCURRENT PROTECTION |
| | FOR THE FEEDERS AND THE 50 AMP SUB-PANEL "A-1". NEC |
| | 230.05, 240.4, 240.21 & 408.36 |
| | |
| | 8) THE TOTAL LOAD CALCULATIONS FOR PANEL "A" SHOWN ON |
| | THE PLAN IS MORE THAN 100 AMPS RATING OF THE PANEL. NEC |
| | 408.30 REQUIRES PANELBOARDS TO HAVE A RATING OF NOT |
| | LESS THAN THE MINIMUM FEEDER CAPACITY REQUIRED FOR THE |
| | CALCULATED LOAD. |
| | |
| | 9) THE PANEL SCHEDULE AND LOAD CALCULATIONS FOR PANEL |
| | "A" NEED TO INCLUDE THE 50 AMPS FOR SUB-PANEL "A-1" |
| | THAT IT FEEDS. NEC 408.30 & 408.36 |
| | |