Plan Review Notes
Plan Review Notes For Permit 13040200
Permit Number 13040200
Review Stop E
Sequence Number 3
Notes
Date Text
2013-09-25 08:03:492010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) SPECIFY ON THE PLANS WHETHER THE UNDER-GROUND
 SERVICE LATERAL IS UTILITY (FLORIDA POWER & LIGHT) OR
 CUSTOMER OWNED. IF IT IS CUSTOMER OWNED SPECIFY THE
 SERVICE CONDUCTOR SIZES. NEC 230.31
  
 2) PROVIDE TOTAL SERVICE LOAD (HOUSE LOAD)
 CALCULATIONS. NEC 220.84 (B)
  
 3) SPECIFY THE SIZES OF ALL CONDUCTORS ON THE PLANS.
 NEC 310.15
  
 4) SHOW THE LOCATION OF THE HOUSE PANEL "H" ON THE
 PLANS. NEC ARTICLE 408
  
 5) SHOW LOCATION OF THE DISCONNECT/ OVER-CURRENT
 PROTECTION FOR THE 50 AMP HOUSE PANEL "H" ON THE PLANS.
 NEC 230.72, 230.91 & 240.21
  
 6) A 150 AMP DISCONNECT/ OVER-CURRENT PROTECTION IS
 SHOWN FOR THE 100 AMP PANEL "A". COMPLY WITH NEC 408.36
 WHICH REQUIRES THE OVER-CURRENT PROTECTION RATING TO
 NOT BE MORE THAN THE PANEL. PLEASE CORRECT.
  
 7) SHOW THE REQUIRED DISCONNECT/ OVERCURRENT PROTECTION
 FOR THE FEEDERS AND THE 50 AMP SUB-PANEL "A-1". NEC
 230.05, 240.4, 240.21 & 408.36
  
 8) THE TOTAL LOAD CALCULATIONS FOR PANEL "A" SHOWN ON
 THE PLAN IS MORE THAN 100 AMPS RATING OF THE PANEL. NEC
 408.30 REQUIRES PANELBOARDS TO HAVE A RATING OF NOT
 LESS THAN THE MINIMUM FEEDER CAPACITY REQUIRED FOR THE
 CALCULATED LOAD.
  
 9) THE PANEL SCHEDULE AND LOAD CALCULATIONS FOR PANEL
 "A" NEED TO INCLUDE THE 50 AMPS FOR SUB-PANEL "A-1"
 THAT IT FEEDS. NEC 408.30 & 408.36
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]