| Plan Review Notes For Permit 13040200 |
| Permit Number |
13040200 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-07-22 12:38:20 | FBC 2010 EXISTING BUILDING CODE | | | FBC 2010 PLUMBING REVIEW #2 | | | DENIED: | | | | | | NO CHANGE FOUND FROM REVIEW #1 | | | 1. SHEET 3: THE KITCHEN SINK IS NOT PERMITTED IN THE | | | BATHROOM WET VENT SYSTEM. | | | FBC 2010 RESIDENTIAL P3108.1 HORIZONTAL WET VENT | | | PERMITTED. | | | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS | | | LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE | | | VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE | | | CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND | | | FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION | | | OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM | | | FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH | | | DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT | | | INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE | | | FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO | | | THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL | | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL | | | WET VENT. | | | | | | 2. THE DRAWING INDICATES THE SFBC CODE AND MIAMI DADE | | | ORD. THE BUILDING CODE AT THIS TIME IS THE 2010 FLORIDA | | | BUILDING CODE. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|