2013-07-16 13:40:332010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) THE PLANS SHOW TWO 150 AMP ELECTRICAL PANELS LOCATED
 IN UNIT 'A' AND ONLY ONE PANEL SCHEDULE FOR UNIT 'A'.
 PLEASE CLARIFY. CITY AMENDMENTS 107.2.1
  
 2) THE PLANS SHOW THAT THE AIR HANDLER FOR UNIT 'B' IS
 LOCATED IN UNIT 'A'. THIS RESTRICTS ACCESS TO THE
 EQUIPMENT BY THE OCCUPANTS OF THE UNIT THAT IT
 SERVICES. NEC 240.24 (B) NOTE: THE DUCTWORK WILL
 PENETRATE THE ONE HOUR FIRE RATE SEPARATION BETWEEN
 UNITS 'A' AND 'B' REQUIRING FIRE DAMPERS ON THE DUCTS.
  
 3) SHOW COMPLIANCE WITH NEC 250.94 FOR INTERSYSTEM
 BONDING.
  
 4) SHOW COMPLIANCE WITH NEC 210.12 (B) FOR ARC-FAULT
 CIRCUIT INTERRUPTER PROTECTION REQUIRED IN OTHER ROOMS
 AND AREAS IN ADDITION TO BEDROOMS.
  
 5) SHOW COMPLIANCE WITH NEC 406.11 FOR TAMPER RESISTANT
 RECEPTACLES.
  
 6) SPECIFY THE LOCATION OF THE ELECTRICAL PANEL IN UNIT
 'B'. NEC 240.24
  
 7) PROVIDE AN ELECTRICAL PLAN FOR UNIT 'B' OR REVISE
 THE SCOPE OF WORK ON SHEET 2 TO EXCLUDE UNIT 'B'. CITY
 AMENDMENTS 107.2.1
  
 8) SHOW COMPLIANCE WITH FBC R314.3.1 FOR SMOKE ALARMS
 IN UNIT 'B'.
  
 9) A RECEPTACLE IS REQUIRED IN BEDROOMS # 1 AND # 4
 BETWEEN THE CLOSET DOOR AND THE BEDROOM DOOR PER NEC
 210.52 (A).
  
 10) PANEL SCHEDULE FOR UNIT 'A' ONLY LISTS THE CIRCUITS
 FOR TWO OF THE FOUR BEDROOMS. NEC 220.83 PLEASE
 CORRECT.
  
 11) NEC 210.11 (C) (1) REQUIRES A MINIMUM OF TWO 20 AMP
 SMALL APPLIANCE BRANCH CIRCUITS IN EACH UNIT.
  
 12) AFTER ADDING THE CIRCUITS LISTED IN REVIEW COMMENTS
 10 AND 11, PLEASE REVISE THE LOAD CALCULATIONS. NEC
 220.83 (B)
  
 13) THE ELECTRICAL RISER PLAN SHOWS TWO SEPARATE METERS
 WITH TWO SEPARATE SERVICE LATERALS FOR THIS BUILDING.
 NEC 230.2 ALLOWS ONLY ONE SERVICE PER BUILDING. PLEASE
 REVISE RISER PLAN TO SHOW A SINGLE SERVICE DROP OR
 LATERAL SUPPLY TO A DUPLEX METER BASE.
  