| Date |
Text |
| 2013-07-16 13:40:33 | 2010 FBC / 2008 NEC |
| | |
| | DENIED BY ELECTRIC |
| | |
| | 1) THE PLANS SHOW TWO 150 AMP ELECTRICAL PANELS LOCATED |
| | IN UNIT 'A' AND ONLY ONE PANEL SCHEDULE FOR UNIT 'A'. |
| | PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 |
| | |
| | 2) THE PLANS SHOW THAT THE AIR HANDLER FOR UNIT 'B' IS |
| | LOCATED IN UNIT 'A'. THIS RESTRICTS ACCESS TO THE |
| | EQUIPMENT BY THE OCCUPANTS OF THE UNIT THAT IT |
| | SERVICES. NEC 240.24 (B) NOTE: THE DUCTWORK WILL |
| | PENETRATE THE ONE HOUR FIRE RATE SEPARATION BETWEEN |
| | UNITS 'A' AND 'B' REQUIRING FIRE DAMPERS ON THE DUCTS. |
| | |
| | 3) SHOW COMPLIANCE WITH NEC 250.94 FOR INTERSYSTEM |
| | BONDING. |
| | |
| | 4) SHOW COMPLIANCE WITH NEC 210.12 (B) FOR ARC-FAULT |
| | CIRCUIT INTERRUPTER PROTECTION REQUIRED IN OTHER ROOMS |
| | AND AREAS IN ADDITION TO BEDROOMS. |
| | |
| | 5) SHOW COMPLIANCE WITH NEC 406.11 FOR TAMPER RESISTANT |
| | RECEPTACLES. |
| | |
| | 6) SPECIFY THE LOCATION OF THE ELECTRICAL PANEL IN UNIT |
| | 'B'. NEC 240.24 |
| | |
| | 7) PROVIDE AN ELECTRICAL PLAN FOR UNIT 'B' OR REVISE |
| | THE SCOPE OF WORK ON SHEET 2 TO EXCLUDE UNIT 'B'. CITY |
| | AMENDMENTS 107.2.1 |
| | |
| | 8) SHOW COMPLIANCE WITH FBC R314.3.1 FOR SMOKE ALARMS |
| | IN UNIT 'B'. |
| | |
| | 9) A RECEPTACLE IS REQUIRED IN BEDROOMS # 1 AND # 4 |
| | BETWEEN THE CLOSET DOOR AND THE BEDROOM DOOR PER NEC |
| | 210.52 (A). |
| | |
| | 10) PANEL SCHEDULE FOR UNIT 'A' ONLY LISTS THE CIRCUITS |
| | FOR TWO OF THE FOUR BEDROOMS. NEC 220.83 PLEASE |
| | CORRECT. |
| | |
| | 11) NEC 210.11 (C) (1) REQUIRES A MINIMUM OF TWO 20 AMP |
| | SMALL APPLIANCE BRANCH CIRCUITS IN EACH UNIT. |
| | |
| | 12) AFTER ADDING THE CIRCUITS LISTED IN REVIEW COMMENTS |
| | 10 AND 11, PLEASE REVISE THE LOAD CALCULATIONS. NEC |
| | 220.83 (B) |
| | |
| | 13) THE ELECTRICAL RISER PLAN SHOWS TWO SEPARATE METERS |
| | WITH TWO SEPARATE SERVICE LATERALS FOR THIS BUILDING. |
| | NEC 230.2 ALLOWS ONLY ONE SERVICE PER BUILDING. PLEASE |
| | REVISE RISER PLAN TO SHOW A SINGLE SERVICE DROP OR |
| | LATERAL SUPPLY TO A DUPLEX METER BASE. |
| | |