| 2013-07-12 10:09:50 | NOTE: OWNER CHANGED BACK TO TWO FAMILY DWELLING. |
| | |
| | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC-RESIDENTIAL. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 101.4.3 OF 2010 FBC-ENERGY CONSERVATION. PLEASE MAKE |
| | SURE ALL THE INFORMATION IS COMPLETED ON THE FORM AND |
| | IT'S SIGNED BY THE PREPARER AND OWNER/AGENT. (THIS WAS |
| | REQUESTED ON THE A/C REVIEW. THERE IS NO INFORMATION |
| | SUBMITTED FOR THE A/C). |
| | |
| | 2- CLARIFY IF DOING WORK ON THE SECOND FLOOR. SHEET 4 |
| | OF 4 SAYS EXISTING SECOND FLOOR PLAN. SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. IF NO WORK, THEN NO NEED TO PROVIDE |
| | FLOOR PLAN. |
| | |
| | 3- SHEET 1 OF 4: |
| | A) CLARIFY FIRST NOTE UNDER GENERAL NOTES (NEW |
| | CONSTRUCTION). WHAT IT MEANS BY "OR APPROVED WINDOWS". |
| | ACCORDING TO THE SCOPE OF WORK ALL WINDOWS AND DOORS |
| | ARE EXISTING. REVISE AS REQUIRED. |
| | |
| | B) CLARIFY WHAT KIND OF WASHER IS THE ONE SHOWN ON THE |
| | UTILITY AREA. DISH-WASHER OR CLOTHES WASHER? (SHEET 2 |
| | OF 4 SHOWS AN OUTSIDE CLOTHES WASHER. SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ONE |
| | HOUR FLOOR ASSEMBLY SEPARATING THE TWO DWELLINGS. SEE |
| | SEC. R302.3 OF 2010 FBC-RESIDENTIAL. |
| | M E119 OR UL 263. |
| | |
| | 5- WINDOW ON BEDROOM #4 DOESN'T COMPLY WITH THE EGRESS |
| | MIN. HEIGHT REQUIREMENTS OF SEC. R310.1.2 OF 2010 |
| | FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL FOR NEW WINDOW IN BEDROOM |
| | #4 AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC. |
| | 107.3.4.1 CITY AMENDMENTS TO FBC. |
| | |
| | ****NOTE: ALL THE APPLIANCES (WASHER, DRYER AND WATER |
| | HEATERS) THAT ARE GOING TO BE INSTALLED OUTSIDE NEED TO |
| | BE DESIGNED FOR OUTSIDE LOCATIONS. INSPECTOR WILL ASK |
| | FOR MANUFACTURER SPECS AT TIME OF INSPECTION. PLEASE |
| | MAKE SURE THIS INFORMATION IS AVAILABLE FOR THE |
| | INSPECTOR. OTHERWISE INSPECTION WILL BE FAILED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |