Plan Review Notes
Plan Review Notes For Permit 13040200
Permit Number 13040200
Review Stop P
Sequence Number 1
Notes
Date Text
2013-04-19 10:04:20FBC 2010 EXISTING BUILDING CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET 3: THE KITCHEN SINK IS NOT PERMITTED IN THE
 BATHROOM WET VENT SYSTEM.
 FBC 2010 P-909.1 HORIZONTAL WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE
 VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE
 CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND
 FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION
 OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM
 FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH
 DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT
 INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 2. THE DRAWING INDICATES THE SFBC CODE AND MIAMI /DADE
 ORDS. THE BUILDING CODE AT THIS TIME IS THE 2010
 FLORIDA BUILDING CODE.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  