| Date |
Text |
| 2013-04-20 13:24:08 | 724 BRADLEY STREET |
| | PERMIT #13040200 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | *****CHANGE OF OCCUPANCY FROM 1-2 FAMILY DWELLING TO |
| | APARTMENTS***** |
| | |
| | NOTE: ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101 |
| | REFER TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION |
| | WITH FLORIDA AMENDMENTS.) |
| | |
| | DESIGN THE 2010 EDITION OF THE FLORIDA FIRE PREVENTION |
| | CODE WHICH CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND |
| | NFPA 101 WITH FLORIDA AMENDMENTS. |
| | |
| | DRAWING INDICATES THERE ARE STAIRS SERVING ADDITIONAL |
| | APARTMENT(S) ABOVE. PROVIDE A COMPLETE LIFE SAFETY PLAN |
| | INDICATING TOTAL NUMBER OF UNITS, EXIT DOORS, EGRESS |
| | WINDOWS, TRAVEL DISTANCES, STAIRS, HANDRAIL DETAILS, |
| | HORIZONTAL AND VERTICAL FIRE BARRIERS, ETC. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | PROVIDE CARBON MONOXIDE ALARMS AND HARD-WIRED |
| | MULTI-STATION SMOKE ALARMS SHALL BE INSTALLED ON ALL |
| | LEVELS OF THE DWELLING UNIT, INSIDE EACH BEDROOM AND |
| | DIRECTLY OUTSIDE BEDROOM DOORS. |
| | |
| | ALL NEW APARTMENTS SHALL BE PROTECTED THROUGHOUT BY A |
| | SUPERVISED FIRE SPRINKLER SYSTEM PER SECTION 30.3.5. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |
| 2013-04-17 13:25:51 | SEE BUILDING COMMENTS. JG. |