| 2013-04-12 11:57:23 | BUILDING PLAN REVIEW |
| | PERMIT: 113040039 |
| | ADD: 13040039 |
| | CONT: ROBB CONSTRUCTION |
| | TEL: (561)346-9509 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 4/12/2013 |
| | ACTION: DENIED |
| | |
| | 1) THE VALUE ON THE PERMIT IS LISTED AS $2,400 DOLLARS, |
| | THIS WOULD NOT EVEN COVER THE COST FOR THE INTERIOR |
| | DEMOLITION SHOWN ON D 1.1. |
| | W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| | ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| | AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| | A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) PLEASE SHOW THE FURNATURE LAYOUT ON THE LS PLAN, IT |
| | IS UNCLEAR AS TO THE USAGE OF THIS SPACE. PLEASE ALSO |
| | NOTE MISSING EMERGENCY LIGHTS IN THE CORRIDOR ADJACENT |
| | TO THE SERVER ROOM, 2010 FBC-B 1006.1.2. |
| | |
| | 3) MISSING THE EXIT DIRECTIONAL LIGHT THAT LEADS INTO |
| | THE CORRIDOR FROM THE SUPERVISORY AREA. 1006.3.1 EXIT |
| | SIGNS. |
| | |
| | 4) MISSING THE QUALIFIERS SIGNATURE ON THE PERMIT |
| | APPLICATION, A HOLD IS ON THE PERMIT TO NOT ISSUE UNTIL |
| | WE RECEIVE THE QUALIFIERS SIGNATURE. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |