| 2013-04-11 14:23:39 | BUILDING PLAN REVIEW |
| | PERMIT: 13040011 |
| | ADD: 1002 GREEN PINE BLVD # B1 |
| | CONT: H LAYTON MAINGUY GC |
| | TEL: (954)249-8500 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 4/11/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) THE PLANS IN THE TITLEBLOCK INDICATE "FIRE", IS |
| | THERE FIRE DAMAGE TO THE INTERIOR OF THIS UNIT? IF SO |
| | DID THE FIRE BURN THROUGH THE DRYWALL AND REQUIRE FLOOR |
| | TRUSS REPAIR? IF SO WILL NEED AN EGINEERS' DESIGN FOR |
| | THE FLOOR TRUSS REPAIR. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 2) THE PLANS INDICATE EXTERIOR WORK ON THE WINDOWS AND |
| | DOORS, BUT THE PLANS FAIL TO PROVIDE THE WIND DESIGN |
| | CRITERIA FROM WHICH THE PRESSURES WERE DESIGNED? |
| | |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 2.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 2.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | HOW MANY STORIES IS THIS UNIT? NEGATIVE PRESSURES ARE |
| | TAKEN FROM THE MEAN ROOF HEIGTH. |
| | |
| | 2.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) WITHIN THE PRODUCT APPROVALS FOR THE HORIZONTAL |
| | SLIDER WINDOWS AND THE SINGLE HUNG WINDOWS PLEASE |
| | CIRCLE WHICH SERIES WILL BE INSTALLED, THIS IDENTIFIES |
| | THE PRESSURES FOR THAT PARTICULAR MODEL IF IMPACT OR |
| | NOT. 1609.1.2. |
| | |
| | 5) THE WINDOW SCHEDULE INDICATES A TYPE "C" FIXED |
| | WINDOW, BUT WHEN YOU LOOK AT THE FLOOR PLAN THE TYPE |
| | "C" OPENING IS THE FRONT DOOR, DISCREPANCY IN THE |
| | PLANS. 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 6) THE PRODUCT APPROVAL SUBMITTED FOR THE HORIZONTAL |
| | SLIDERS DOES NOT INCLUDE MULLIONS, PLEASE SHOW |
| | COMPLIANCE WITH: |
| | |
| | |
| | |
| | 7A) SHEET A-1.0 NOTE # 6 REFERENECES CODE SECTION |
| | 402.1.6.3 BUT DOES NOT LIST WHICH CODE? BUILDING OR |
| | RESIDENTIAL, NO SUCH SECTION. |
| | 2010 FBC-B 1715.5.5.1 MULLIONS. |
| | MULLIONS OR MULLED FENESTRATION ASSEMBLIES SHALL BE |
| | TESTED BY AN APPROVED TESTING LABORATORY IN ACCORDANCE |
| | WITH EITHER AAMA 450, ASTM E 330, OR TAS 202 (HVHZ |
| | SHALL COMPLY WITH TAS 202), OR SHALL BE ENGINEERED IN |
| | ACCORDANCE WITH AAMA 450 USING ACCEPTED ENGINEERING |
| | PRACTICE. MULLIONS TESTED AS STAND-ALONE UNITS OR |
| | QUALIFIED BY ENGINEERING SHALL USE PERFORMANCE CRITERIA |
| | CITED IN SECTIONS 1715.5.5.2, 1715.5.5.3 AND |
| | 1715.5.5.4. MULLIONS QUALIFIED BY AN ACTUAL TEST OF AN |
| | ENTIRE ASSEMBLY SHALL COMPLY WITH SECTION 1715.5.5.4, |
| | EXCEPT THAT MULLIONS IN ASSEMBLIES REQUIRING A |
| | DEFLECTION LIMITATION, AS DEFINED IN AAMA/WDMA/CSA |
| | 101/I.S.2/A440, SHALL MEET 1715.5.5.2 AND 1715.5.5.3. |
| | PRODUCTS NOT INCLUDED WITHIN THE SCOPE OF SECTION |
| | 1715.5.5.1 SHALL COMPLY WITH SECTIONS 1715.5.5.3 AND |
| | 1715.5.5.4. |
| | 1715.5.5.2 LOAD TRANSFER. |
| | 1715.5.5.3 DEFLECTION. |
| | 1715.5.5.4 STRUCTURAL SAFETY FACTOR. |
| | 1715.5.5.4 STRUCTURAL SAFETY FACTOR. |
| | |
| | 7B) SHEET A-1.0 NOTE # 6 ALSO REFERENCES CODE SECTION |
| | R303 WHICH IS THE ONE & TWO FAMILY RESIDENTIAL CODE, |
| | THIS IS A CONDOMINIUM (R2) WHICH FALLS UNDER THE 2010 |
| | FBC-B. |
| | |
| | 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |