| Plan Review Notes For Permit 13030854 |
| Permit Number |
13030854 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-08-13 17:05:11 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRICAL | | | | | | 1) SUBMIT VOLTAGE DROP CALCULATIONS FOR PANEL A FEEDERS | | | TO SHOW EFFICIENCY OF OPERATION. CITY AMENDMENTS | | | 107.2.1.3 | | | | | | 2) NEC TABLE 310.15 (B) (6) CAN NOT BE USED TO SIZE THE | | | CONDUCTORS TO THE TWO PANELBOARDS. THE EXCEPTION | | | REQUIRES ONE PANELBOARD TO SUPPLY ALL LOADS ASSOCIATED | | | WITH THE DWELLING UNIT. NEC TABLE 310.16 IS REQUIRED TO | | | BE USED TO SIZE THE CURRENT CARRYING CONDUCTORS. | | | | | | 3) SPECIFY THE LENGTH OF TAPS PER NEC 240.21. | | | | | | 4) THE EQUIPMENT GROUNDING CONDUCTORS ARE REQUIRED TO | | | BE SIZED IN ACCORDANCE WITH NEC 250.122. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|