| 2013-07-30 16:24:38 | RESIDENTIAL (R3) ADDITION, BUILDING 1ST RE-SUBMITTAL | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- REVISE THE DESIGN PRESSURES SHOWN ON THE WINDOW | | | SCHEDULE ON SHEET A-5. SOME WINDOWS ARE ON ZONE 4 AND | | | SOME ARE ON ZONE 5. DESIGN PRESSURES SHOWN ARE FOR ZONE | | | 4 ONLY. SEE FIGURE R301.2(7) OF 2010 FBC-RESIDENTIAL | | | AND REVISED DESIGN PRESSURES ON SHEET S-1. | | | | | | 2- REVISE RAS 117 CALCULATIONS FOR BUILT UP ROOFING: | | | | | | A) FASTENER SPACING NEEDS TO BE ROUNDED DOWN AS | | | REQUIRED BY SEC. 10.4.5 OF RAS 117. | | | | | | B) CLEARLY SPECIFY FASTENER SPACING AT THE LAP AND | | | NUMBER OF ROWS AND FASTENER SPACING IN THE FIELD OF THE | | | BASE SHEET. CALCULATIONS SUBMITTED ARE MISSING THIS | | | INFORMATION. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|