| 2013-04-06 12:25:24 | 2100 45TH STREET - SUITE A8 | | | TRACKING #13030837 | | | PERMIT #13010919 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | HAZARD SEPARATION IS REQUIRED PER NFPA 101 SECTION | | | 39.3.2.1. ANY AREA (STORAGE) HAVING A DEGREE OF HAZARD | | | GREATER THAN NORMAL TO THE GENERAL OCCUPANCY (BUSINESS) | | | OF THE SPACE, SHALL BE SEPARATED FROM NON-STORAGE AREAS | | | WITH A 1-HOUR FIRE-RATED BARRIER OR BE PROTECTED WITH | | | AN AUTOMATIC SPRINKLER SYSTEM. DOORS SHALL BE SELF | | | CLOSING, POSITIVE LATCHING, AND FIRE-RATED FOR AT LEAST | | | 45-MINUTES PER SECTION 8.7 OF NFPA 101. | | | | | | EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH | | | SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL | | | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN | | | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE | | | SPACED NOT MORE THAN 15 FEET ON CENTER. REFERENCE | | | SECTION 8.3.2.4 OF FLORIDA FIRE PREVENTION CODE - NFPA | | | 101 | | | | | | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL | | | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. REFERENCE | | | SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION CODE - NFPA | | | 101 | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | | | | |
|