| Plan Review Notes For Permit 13030820 |
| Permit Number |
13030820 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-04-22 12:44:24 | 6701 NORTH JOG ROAD - MAINTENANCE BUILDING | | | TRACKING #13030820 | | | PERMIT #12030240 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET A5-100: THE BUILDING CLASSIFICATION FAILS TO | | | CLASSIFY THE BREAK ROOM AS AN ASSEMBLY OCCUPANCY. THIS | | | SPACE APPEARS TO BE APPROXIMATELY 900 SQUARE FEET WITH | | | AN OCCUPANT LOAD OF APPROXIMATELY 60 PERSONS FIGURED AT | | | 15 SQ.FT. PER PERSON. PROVIDE THE TRAVEL DISTANCES, | | | DEAD-END, COMMON PATH OF TRAVEL, ETC. INFORMATION FOR | | | ASSEMBLY OCCUPANCIES. FOR NONSEPARATED MIXED USE | | | OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE SAFETY | | | REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO THE | | | BUILDING. | | | | | | SHEET A5-100:THE BREAK ROOM IS AN ASSEMBLY OCCUPANCY | | | WITH AN OCCUPANT LOAD OF APPROXIMATELY 60 PERSONS; | | | THEREFORE, TWO EXITS ARE NEEDED FROM THE BREAK ROOM AND | | | THE BREAKROOM DOORS SHALL SWING IN THE DIRECTION OF | | | EGRESS. | | | | | | SHEET A5-100: ASSEMBLY OCCUPANCIES WITH AN OCCUPANT | | | LOAD ABOVE 50 PERSONS REQUIRE THE DOOR LOCKS AND | | | LATCHES TO BE RELEASED BY PANIC OR FIRE EXIT HARDWARE. | | | BECAUSE THIS IS A NON-SEPARATED USE BUILDING, ALL EXIT | | | AND EXIT ACCESS DOORS WILL REQUIRE PANIC/FIRE EXIT | | | HARDWARE. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|