2013-04-22 12:44:246701 NORTH JOG ROAD - MAINTENANCE BUILDING
 TRACKING #13030820
 PERMIT #12030240
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A5-100: THE BUILDING CLASSIFICATION FAILS TO
 CLASSIFY THE BREAK ROOM AS AN ASSEMBLY OCCUPANCY. THIS
 SPACE APPEARS TO BE APPROXIMATELY 900 SQUARE FEET WITH
 AN OCCUPANT LOAD OF APPROXIMATELY 60 PERSONS FIGURED AT
 15 SQ.FT. PER PERSON. PROVIDE THE TRAVEL DISTANCES,
 DEAD-END, COMMON PATH OF TRAVEL, ETC. INFORMATION FOR
 ASSEMBLY OCCUPANCIES. FOR NONSEPARATED MIXED USE
 OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE SAFETY
 REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO THE
 BUILDING.
  
 SHEET A5-100:THE BREAK ROOM IS AN ASSEMBLY OCCUPANCY
 WITH AN OCCUPANT LOAD OF APPROXIMATELY 60 PERSONS;
 THEREFORE, TWO EXITS ARE NEEDED FROM THE BREAK ROOM AND
 THE BREAKROOM DOORS SHALL SWING IN THE DIRECTION OF
 EGRESS.
  
 SHEET A5-100: ASSEMBLY OCCUPANCIES WITH AN OCCUPANT
 LOAD ABOVE 50 PERSONS REQUIRE THE DOOR LOCKS AND
 LATCHES TO BE RELEASED BY PANIC OR FIRE EXIT HARDWARE.
 BECAUSE THIS IS A NON-SEPARATED USE BUILDING, ALL EXIT
 AND EXIT ACCESS DOORS WILL REQUIRE PANIC/FIRE EXIT
 HARDWARE.
  