| 2013-03-28 15:14:20 | 13030792 | | | 1006 HENRIETTA AVE. | | | ELECTRIC SERVICE | | | | | | PLEASE REVISE THE PLAN IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. THE SCOPE OF ELECTRICAL | | | WORK PROPOSED IS NOT CLEAR. IS THE ELECTRICAL SERVICE | | | NEW OR IS THIS A REPAIR TO AN EXISTING SERVICE? | | | | | | PROVIDE AN ELECTRICAL RISER PLAN FOR THE SERVICE. NEC | | | 215.5 | | | | | | SHOW LOCATION OF ALL SERVICE DISCONNECTS. A BUILDING OR | | | OTHER STRUCTURE SERVED SHALL BE SUPPLIED BY ONLY ONE | | | SERVICE. MAIN DISCONNECTS SHALL BE GROUPED IN ONE | | | LOCATION. NEC 230.2 | | | | | | PROVIDE A GROUND ROD AND GROUNDING ELECTRODE FOR THE | | | ELECTRIC SERVICE. NEC 250.32 | | | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND. NEC 250.94 | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|