| | FBC 2010 EXISTING BUILDING CODE |
| | FBC 2010 ACCESSIBILITY CODE |
| | FBC 2010 PLUMBING REVIEW #1 |
| | |
| | 1. PLEASE SUBMIT THE DATA REQUIRED FOR THE SOVENT |
| | SYSTEM. IF THE SOVENT IS CONINE, DE-AERATOR RULE (D): |
| | SOIL AND WASTE BRANCHES MAY CONNECT TO THE SOVENT |
| | BUILDING DRAIN BETWEEN THE CENTERLINE OF THE STACK AND |
| | THE TERMINATION POINT OF THE PRESSURE RELIEF LINE |
| | (PRL). ALL CONNECTIONS SHALL BE MADE A MINIMUM DISTANCE |
| | OF TEN PIPE |
| | DIAMETERS (BASED ON STACK SIZE) DOWNSTREAM FROM THE |
| | CENTERLINE OF THE STACK. SOIL AND WASTE BRANCHES SHALL |
| | NOT CONNECT |
| | WHERE THE SOVENT BUILDING DRAIN MAKES A HORIZONTAL |
| | CHANGE OF DIRECTION (EXAMPLE ON P2.1 S6) |
| | |
| | P-714.4.3 TECHNICAL DATA. THE REGISTERED DESIGN |
| | PROFESSIONAL SHALL SUBMIT SUFFICIENT TECHNICAL DATA TO |
| | SUBSTANTIATE THE PROPOSED ALTERNATIVE ENGINEERED DESIGN |
| | AND TO PROVE THAT THE PERFORMANCE MEETS THE INTENT OF |
| | THIS CODE. |
| | |
| | 2. SHEET A4.10 THE COMMON AREA TOILET ROOMS ARE TO BE |
| | BETWEEN 16" - 18" MAX. OFF THE SIDE WALL. ACCESSABILITY |
| | 604.2 LOCATION. |
| | |
| | *PROVISO* |
| | FOR THE DOMESTIC PUMPS SHOWN ON P0.2: |
| | 606.5.5 LOW-PRESSURE CUTOFF REQUIRED ON BOOSTER PUMPS. |
| | A LOW-PRESSURE CUTOFF SHALL BE INSTALLED ON ALL BOOSTER |
| | PUMPS IN A WATER PRESSURE BOOSTER SYSTEM TO PREVENT |
| | CREATION OF A VACUUM OR NEGATIVE PRESSURE ON THE |
| | SUCTION SIDE OF THE PUMP WHEN A POSITIVE PRESSURE OF 10 |
| | PSI (68.94 KPA) OR LESS OCCURS ON THE SUCTION SIDE OF |
| | THE PUMP. |
| | |
| | REVIEW BY |
| | LARRY WAGNER |
| | CHIEF PLUMBING INSPECTOR |