| 2013-04-17 16:58:52 | BUILDING PLAN REVIEW |
| | PERMIT: 13030782 |
| | ADD: 326 FERN ST |
| | CONT: STRATICON, LLC |
| | TEL: (772)210-0200 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: APRIL 17/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A0.01: |
| | 1A) PLEASE REVISE THE GENERAL PROJECT INFORMATION NOTE, |
| | THAT INDICATES THE SCOPE OF THESE DRAWINGS ARE FOR |
| | INTERIOR DEMOLITION ONLY. |
| | |
| | 1B) PROJECT SPECIFIC CODE SUMMARY INDICATE THIS PROJECT |
| | WAS DESIGNED AS A LEVEL II ALTERATION. PLEASE REFER TO |
| | THE 2010 EXISTING BUILDING CODE SECTION 901.3 CHANGE OF |
| | OCCUPANCY CLASSIFICATION. WHERE THE OCCUPANCY |
| | CLASSIFICATION OF A BUILDING CHANGES, THE PROVISIONS OF |
| | SECTIONS 902 THROUGH 912 SHALL APPLY. THIS INCLUDES A |
| | CHANGE OF OCCUPANCY CLASSIFICATION WITHIN A GROUP AS |
| | WELL AS A CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE |
| | GROUP TO A DIFFERENT GROUP. |
| | |
| | 1C) THIS STRUCTURE IS ALSO CLASSIFIED AS A HISTORIC |
| | STUCRTURE PLEASE INDICATE WHICH METHOD OF COMPLIANCE |
| | YOU WOULD BE CLAIMING UNDER THE HISTORICAL DESIGNATION. |
| | SECTION 1104 EQUIVALENCY, SECTION 1105 COMPLIANCE OR |
| | SECTION 1106 INVESTIGATION AND EVALUATION. |
| | |
| | 1D) THE COVERSHEET ALSO REFERENECES THE PALM BEACH |
| | COUNTY AMENDMENTS. THE PALM BEACH COUNTY AMENDMENTS |
| | WILL ONLY PERTAIN TO |
| | CHAPTER 1 AND ONLY IF THIS PROJECT WAS LOCATED IN THE |
| | COUNTY. THE CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | PLEASE UPDATE. |
| | |
| | 1E) THE FINISH FLOOR OF THE SIXTH FLOOR IS 76'-0" ABOVE |
| | GRADE AND MEETS THE DEFINITION OF HIGHRISE DEFINITION |
| | 202 FBC-B. |
| | |
| | 2) THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING. |
| | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 2B) THRESHOLD INSPECTOR: |
| | WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. |
| | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| | BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 2C) THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | ------------------------------------------------------- |
| | ----------------------------------- |
| | |
| | 2D) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | ------------------------------------------------------- |
| | ------------------------------------- |
| | |
| | 2E) A THRESHOLD PLAN REVIEW STOP WILL BE ADDED TO THE |
| | PLAN REVIEW FOR THIS PROJECT UNTIL THESE ITEMS ARE |
| | COMPLETED AS REQUESTED BY THE CHIEF BUILDING INSPECTOR |
| | KEN CONRAD: |
| | |
| | PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 2E)(1)) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| | CONRAD: [email protected] |
| | |
| | 2E)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A |
| | RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. |
| | THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 3) SHEET A2.001 LS- BASEMENT: |
| | 3A) THE STAIRWELL # 1 HAS THE ELEVATOR LOCATED IN THE |
| | VERTICAL EXIT. 2010 EXISTING BUILDING CODE |
| | 912.1.1COMPLIANCE WITH CHAPTER 8. |
| | SEE COMPLIANCE WITH 801.2 COMPLIANCE. IN ADDITION TO |
| | THE PROVISIONS OF THIS CHAPTER, WORK SHALL COMPLY WITH |
| | ALL OF THE REQUIREMENTS OF CHAPTERS 6 AND 7. THE |
| | REQUIREMENTS OF SECTIONS 703, 704, AND 705 SHALL APPLY |
| | WITHIN ALL WORK AREAS WHETHER OR NOT THEY INCLUDE EXITS |
| | AND CORRIDORS SHARED BY MORE THAN ONE TENANT AND |
| | REGARDLESS OF THE OCCUPANT LOAD. 703.2.1 EXISTING |
| | VERTICAL OPENINGS. |
| | ALL EXISTING INTERIOR VERTICAL OPENINGS CONNECTING TWO |
| | OR MORE FLOORS SHALL COMPLY WITH THE APPROPRIATE |
| | SECTIONS OF THE FLORIDA FIRE PREVENTION CODE. 2010 |
| | FBC-B 10.22.3 ELEVATORS SHALL NOT OPEN INTO AN EXIT |
| | ENCLOSURE. |
| | |
| | 3B) NEITHER THIS SHEET NOR A2.01 SHOW THE WALLS OR |
| | OPENING PROTECTIVES TO BE FIRE RATED BARRIERS. 2010 |
| | FBC-B 913.2.1 PROTECTION OF FIRE PUMP ROOMS. |
| | FIRE PUMPS SHALL BE LOCATED IN ROOMS THAT ARE SEPARATED |
| | FROM ALL OTHER AREAS OF THE BUILDING BY 2-HOUR FIRE |
| | BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR |
| | 2-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE |
| | WITH SECTION 712, OR BOTH. EXISTING BUILDING CODE |
| | 912..2 FIRE PROTECTION SYSTEMS. |
| | |
| | 4) SHEET A2.002 LS- 1ST FLOOR: |
| | 4A) FIRE COMMAND ROOM FBC-B 403.4.5 SEE SECTION 911 1 |
| | HOUR FIRE SEPERATION. |
| | |
| | 4B) THE AREA LISTED AS MERCANTILE OR RESTARAUNT MAY |
| | ALSO MEET THE OCCUPANCY LOAD FOR AN A2 ASSEMBLY IF THE |
| | OCCUPANT LOAD IS OVER 50. |
| | THE IF THE RESTARAUNT IS LESS THAN 50 IT WILL BE |
| | CONSIDERED MERCANTILE. THE OCCUPANT LOADING FOR |
| | MERCANTILE AT GRADE IS 30 SQ FT / OCCUPANT BUT THE A2 |
| | ASSEMBLY IS FIGURED AT 15 SQ FT / OCCUPANT IF THE SPACE |
| | IS GOING TO SELL GROCERCIES IT WILL BE CONSIDERED |
| | MERCANTILE |
| | BUT IF THE RENTAL SPACE WILL BE CONSIDERED A RESTARAUNT |
| | USE THE 15 SQ FT /OCCUPANT. 2010 FBC-B TABLE 1004.1.1. |
| | |
| | 4C) THE OCCUPANCY SEPERATION WALL BETWEEN THE R2 |
| | OCCUPANCY AND THE BUSINESS & ASSEMBLY (COMMUNITY ROOM # |
| | 102) IS NOT A CONTINIOUS SEPERATION AND OR OPENING |
| | PROTECTIVES, PLEASE IDENTIFY? 2010 FBC-B TABLE 508.4 & |
| | TABLE 715.4. |
| | |
| | 4D) FOR BOTH VERTICAL EXITS THAT OPEN ONTO THIS FLOOR |
| | AND THEN CONTINUE INTO THE BASEMENT, PLEASE PLACE EXIT |
| | DIRECTIONAL SIGNAGE PER |
| | (2010 FBC-B 1022.7) TO PREVENT PERSONS FROM |
| | UNINTENIONALLY CONTINUING INTO LEVELS BELOW GRADE. |
| | |
| | 4E) ALSO REVIEW FBC-B 1009.6.4 STAIR IDENTIFICATION & |
| | 1022.8 FLOOR IDENTIFICATION. |
| | |
| | 4F) CODE ANALYSIS NOTE # 5 INDICATES SOUND TRANSMITION |
| | FBC-B1207.2 BUT NO COMMENT TO FBC-B 1207.3 AND |
| | COMPLIANCE WITH : |
| | 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 5) SHEET A2.00.3 LS 2ND FLOOR: |
| | 5A) COMMON STATEMENT FOR THE 2ND -6TH FLOOR. PLANS ARE |
| | MISSING THE ELEVATOR LOBBY FBC-B 708.14.1. 2010 |
| | EXISTING BLDG CODE SECTION |
| | 703.2.2. SUPPLEMENTAL SHAFT AND FLOOR OPENING ENCLOSURE |
| | REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS |
| | 50 PERCENT OF THAT FLOOR AREA, THE ENCLOSURE |
| | REQUIREMENTS OF SECTION 703.2 SHALL APPLY TO VERTICAL |
| | OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE FLOOR. |
| | |
| | 5B) COMMON STATEMENT FOR THE 2ND -6TH FLOOR AT GRID |
| | LINES E BETWEEN 4 &5. THIS AREA IS SHARED BETWEEN 3 |
| | TENANTS, THE CONCERN IS IF A FIRE IS STARTED WITHIN |
| | THIS AREA THE THREE UNITS WILL BE EFFECTED BY NOT |
| | HAVING FIRE RATED GLASS IN THE WINDOWS & DOORS. THE |
| | PLANS DO STATE THESE OPENINGS WILL HAVE LARGE MISSILE |
| | IMPACT RESISTANT GLAZING IN THE OPENINGS, WE WOULD BE |
| | LESSS CONCERNED WITH THE FIRE RATED GLASS IF THIS AREA |
| | IS TO BE FIRE SPRINKLERED SINCE THERE ARE CURRENTLY NO |
| | FIRE SPRINKLER PLANS THAT WERE SUBMITTED IN THIS SET OF |
| | PLANS. FBC-B 403.3. |
| | |
| | 6) SHEET A3.01.1 & A3.01.2ELEVATIONS, PRESSURES & |
| | PRODUCT APPROVALS: |
| | 6A) THE LIST OF PRODUCT APPROVALS IS NOT ENOUGH TO BE |
| | ABLE TO DO A COMPLETE REVIEW OF THE LISTED PRODUCTS. |
| | THE CITY WILL REQUIRE PRODUCT APPROVALS FOR ALL |
| | COMPONENTS AND CLADDING THAT WILL BE INSTALLED ON THE |
| | EXTERIOR OF THIS PROJECT. A LIST IS NOT SUFFICIENT |
| | ENOUGH, TO BE ABLE TO DO A REVIEW OF THE PRODUCT. (3) |
| | COPIES OF EACH PRODUCT WILL BE REQUIRED SINCE THIS IS A |
| | THRESHOLD BUILDING. 2010 WPB ADMIN CODE 107.3 |
| | EXAMINATION OF DOCUMENTS/ 2010 FBC-B 1609.6.4.4.1. |
| | COMPONENTS & CLADDING. |
| | |
| | 6B) FOR GLAZING PRODUCT APPROVALS PLEASE CIRCLE THE |
| | LENGTH, WIDTH, TYPE OF GLAZING, MULLIONS AND PRESSURES |
| | SO WE WILL KNOW WHICH OPTIONS YOU ARE SELECTING. |
| | |
| | 6C) ROOFING PRODUCT APPROVALS, WILL HAVE VARIOUS |
| | SUB-SYSTEMS THAT CAN BE INSTALLED UNDER VARYING |
| | CONDITIONS AND ASSOCATED PRESSURES. PLEASE HIGHLIGHT |
| | WHICH OF THESE SUB-SYSTEMS WILL BE INSTALLED ON THIS |
| | PROJECT, IF MORE THAN ONE SUB-SYSTEM WILL BE INSTALLED |
| | PLEASE IDENTIFY EACH AND THE LOCATION OF THE |
| | INSTALATION. NOTE IF THE PRODUCT APPROVALS HAS |
| | LIMITATIONS ON ENHANCED FASTENING IN ZONES 2 & 3. IF |
| | ALLOWED PROVIDE RAS 117 CALCULATIONS PREPARED BY A |
| | DESIGN PROFESSIONAL. 1609.6.4.3. |
| | |
| | 6D) PLEASE NOTE THE LISTED PRODUCT NOA 09-0804.05 ROOF |
| | TOP A/C RACK +/- 75 , SHEET S0.02 INDICATES TTHE ROOF |
| | TOP PRESSUES IN VULT |
| | ZONE 1 VULT -122.1= -73,26 VASD |
| | ZONE 2 &3 VULT -191.7= -115.02 VASD |
| | PLEASE ALSO REVIEW FBC-B 1609.8 FOR ROOF TOP STRUCTURES |
| | AND EQUIPMENT AAND MULTIPLIERS TO BE USED. |
| | IT APPEARS THIS PRODUCT WILL NOT MEET THE ASSOCIATED |
| | PRESSURES FOR ANY ZONE. THERE ARE ALOT OF A/C ROOFTOP |
| | UNITS THAT ARE LOCATED WITHIN ZONE 2 WITH THE INCREASED |
| | PRESSURES. |
| | |
| | 6E) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6F) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES ROOFTOP EQUIPMENT/ |
| | EXHAUST FANS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 6G) SHEET SHEET A3.01.2 DETAIL SOUTH ELEVATION BALCONY |
| | AREA, PLEASE PROVIDE A SUMMARY OF PRESSURES FOR THE |
| | INSET BALCONY AREA. WIND DESIGN IS TO BE TAKEN FORM ALL |
| | DIRECTIONS, IF SUCH WHEN THE WIND WOULD BE FROM THE |
| | SOUTHEAST THIS AREA IS LIKE A PARTIALLY ENCLOSED |
| | BUILDING THAT WILL ALLOW THE WIND TO ENTER AND |
| | PRESSUREIZE THIS AREA GREATER THAN THE SURROUNDING |
| | SURFACES WHERE THE WIND WOULD BE ABLE TO RACE ACROSS |
| | THE FRONT. THE SECOND EFFECT IS IF THE WIND DIRECTION |
| | IS FROM THE NORTH EAST WHERE A VENTURI-EFFECT TAKES |
| | PLACE SIMILAR TO AN END ZONE WHERE THE NEGATIVE |
| | PRESSURES WILL BE HIGHER? 1609.4.1 WIND DIRECTION AAND |
| | SECTORS. |
| | |
| | 7) SHEET A4.02N DOOR # 21A IS MISSING FIRE RATING PER |
| | FBC-B 911.1.2 OPENING PROTECTION TABLE 715.4. |
| | |
| | 8SHEET A4.02S DOOR # 19 STAAIRWELL DOOR MISSING FIRE |
| | RATING OPENING PROTECTIVES T 715.4. |
| | |
| | 9) SHEET A4-10 : |
| | 9A) LOBBY TOILET ROOM INDICATES THE ACCESSIBLE WATER |
| | CLOSET IS 1'-8" AWAY FROM THE SIDE WALL NOT 18" PLEASE |
| | SEE 2010 FL ACC CODE 604.2. |
| | |
| | 9B) DETAIL # 7 RETAIL WATER CLOSET ROOM IS INDICATED TO |
| | BE 2'-0" AWAY FROM THE SIDE WALL. 2010 FL ACC CODE |
| | 604.2. |
| | |
| | 10) A8.01 DETAIL 4 WALL TYPE A.4 DOES NOT PROVIDE THE |
| | FBC-B 1207.2 AIR-BORNE SOUND. |
| | |
| | 11) SHEET A8.02 WINDOW BUCK DETAILS INDICATE A BEVELED |
| | BUCK THAT DOES NOT EXTEND TO THE BACK WINDOW FLANGE, NO |
| | SUPPORT. FBC-B 1715.5.4.2 MASONRY, CONCRETE OR OTHER |
| | STRUCTURAL SUBSTRATE. UNLESS OTHERWISE TESTED, BUCKS |
| | SHALL EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR |
| | DOOR FRAME SUCH THAT FULL SUPPORT OF THE FRAME IS |
| | PROVIDED. SHIMS SHALL BE MADE FROM MATERIALS CAPABLE OF |
| | SUSTAINING APPLICABLE LOADS, LOCATED AND APPLIED IN A |
| | THICKNESS CAPABLE OF SUSTAINING APPLICABLE LOADS. |
| | ANCHORS SHALL BE PROVIDED TO TRANSFER LOAD FROM THE |
| | WINDOW OR DOOR FRAME ASSEMBLY TO THE SECURED WOOD BUCK. |
| | |
| | 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |