Plan Review Notes
Plan Review Notes For Permit 13030746
Permit Number 13030746
Review Stop B
Sequence Number 2
Notes
Date Text
2013-05-09 13:54:58RESIDENTIAL (R3) REPAIRS SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- SPECIFY TYPE OF EXISTING BEDROOM WINDOWS TO BE
 REPLACED TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS. SEC. 604 OF 2010 FBC-EXISTING BUILDING.
  
 ***NOTE: ONLY THE SIZE OF WINDOWS WAS PROVIDED. TYPE OF
 EXISTING WINDOWS WAS NOT PROVIDED.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FLAT ROOF. CLEARLY SPECIFY WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED AND PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS IF THE PRODUCT APPROVAL SUBMITTED
 REQUIRES SIGNED AND SEALED CALCULATIONS.
  
 ***NOTE: ROOFING CONTRACTOR IS REQUIRED TO APPLY FOR
 THE ROOFING PERMIT.
  
 ***NOTE: THIS MAY BE PROVIDED BY THE ROOFING CONTRACTOR
 WHEN APPLYING FOR THE ROOFING PERMIT. THIS NOTE WILL BE
 REMOVED WHEN ITEM #1 ABOVE IS PROVIDED AND ROOFING
 CONTRACTOR PROVIDE THE REQUIRED INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712