| Date |
Text |
| 2013-04-01 13:16:43 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | ELECTRICAL REVIEW COMMENTS. |
| | |
| | ELECTRICAL PLANS ARE REQUIRED. PROVIDE AN ELECTRICAL |
| | RISER PLAN SHOWING THE PANEL, MAIN BREAKER, GROUNDING, |
| | FEEDERS AND BRANCH CIRCUITS. INCLUDE A LOAD CALCULATION |
| | AND PANEL DIRECTORY. SHOW LOCATION OF THE ELECTRICAL |
| | PANEL WITH REQUIRED SAFE WORKING CLEARANCES. INDICATE |
| | THE SIZE AND LOCATION OF THE ELECTRICAL PANEL. ON A |
| | FLOOR PLAN SHOW THE LOCATION OF ALL NEW LIGHTING |
| | OUTLETS, RECEPTACLE OUTLETS AND SMOKE DETECTORS. NEC |
| | 215.5, 210.50, 110.26. 107.2.1 |
| | |
| | SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI |
| | PROTECTED. NEC 210.8 |
| | |
| | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS |
| | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON |
| | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 |
| | |
| | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| | |
| | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW |
| | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 |
| | |
| | THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH |
| | CIRCUIT. NEC 210.11 (C) (3) |
| | |
| | A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE |
| | FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1) |
| | |
| | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| | SERVICE GROUND. NEC 250.94 |
| | |
| | |
| | |
| | ROBERT LECKY |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6718 |
| | |
| | |