2013-04-01 16:21:36RESIDENTIAL (R3) REPAIRS BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FLAT ROOF. CLEARLY SPECIFY WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED AND PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS IF THE PRODUCT APPROVAL SUBMITTED
 REQUIRES SIGNED AND SEALED CALCULATIONS.
  
 ***NOTE: ROOFING CONTRACTOR IS REQUIRED TO APPLY FOR
 THE ROOFING PERMIT.
  
 B) GARAGE DOOR THAT MEETS THE DESIGN PRESSURES. NOTE:
 THIS BUILDING IS LOCATED ON EXPOSURE "C". FLORIDA
 PRODUCT APPROVAL FL15279 SUBMITTED DOESN'T MEET THE
 REQUIRED DESIGN PRESSURES FOR EXPOSURE "C".
  
 2- SPECIFY TYPE AND SIZE OF EXISTING BEDROOM WINDOWS TO
 BE REPLACED TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS. SEC. 604 OF 2010 FBC-EXISTING BUILDING.
  