Plan Review Notes
Plan Review Notes For Permit 13030710
Permit Number 13030710
Review Stop B
Sequence Number 1
Notes
Date Text
2013-04-16 12:36:47****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS. IF
 NON COMPLIANT EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 PROPOSED, ALSO NOTE EXISTING CONDITIONS (TYPE OF
 WINDOW) AND EXISTING CLEAR OPENING SIZE AND PROPOSED
 CLEAR OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB
 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN
 5%.
  
 2. PROVIDE A COPY OF TH CONTRACT FOR THIS JOB FBC 109.
  
 3. TWO SETS REQUIRED; ONLY ONE SET OF WINDOW PRODUCT
 APPROVALS WAS SUBMITTED. THREE SETS OF THE SLIDING
 GLASS DOOR NOA WAS SUBMITTED. FBC 107.