| Plan Review Notes For Permit 13030652 |
| Permit Number |
13030652 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-03-26 12:09:15 | | | | THE FOLLOWING NOTE WAS PLACED ON THE PLANS. | | | | | | WIRING IN ALL PATIENT CARE AREAS / EXAM ROOMS REQUIRES | | | A SPECIFIC LISTED WIRING METHOD THAT PROVIDES REDUNDANT | | | GROUNDING AND INCLUDES AN INSULATED COPPER EQUIPMENT | | | GROUND. NEC 517.13 | | | | | | |
|