Plan Review Notes
Plan Review Notes For Permit 13030651
Permit Number 13030651
Review Stop E
Sequence Number 1
Notes
Date Text
2013-03-27 13:46:31PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 WIRING IN ALL PATIENT CARE AREAS / EXAM ROOMS REQUIRES
 A SPECIFIC LISTED WIRING METHOD THAT PROVIDES REDUNDANT
 GROUNDING AND INCLUDES AN INSULATED COPPER EQUIPMENT
 GROUND. NEC 517.13
  
 NOTE: SHEET A7 WITH POWER PLAN DOES NOT APPEAR WITH THE
 ELECTRICAL PLANS?
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved