| 2013-06-03 14:05:53 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | PLEASE NOTE THAT COMMENTS SHOULD BE ADDRESSED BY |
| | REVISING THE PLAN TO SHOW CODE COMPLIANCE. A |
| | TRANSMITTAL LETTER IS HELPFUL FOR PLAN REVIEW. SOME OF |
| | THE COMMENTS WERE ADDRESSED WITH A PARAGRAPH ON THE |
| | RESUBMITTAL FORM. SEE FBC 107, PLANS TO CLEARLY SHOW |
| | SCOPE OF WORK AND CODE COMLIANCE. |
| | |
| | COMMENTS FROM PREVIOUS LISTS: |
| | |
| | 1. IT APPEARS THAT ONE UNIT IS TO BE SPLIT INTO TWO |
| | UNITS. REVISE THE PLAN TO SHOW EXITING FOR UNIT 103. AS |
| | DRAWN, THEY NOW NEED TO EXIT THROUGH UNIT 104. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. |
| | 3RD REVIEW, NOT ADDRESSED. THE RESUB SHEET STATES THAT |
| | 104 IS NOT BEING SPLIT. IT IS NOT CLEAR HOW EXITING FOR |
| | 103 IS AFFECTED AS THE ONLY EXIT SHOWN FOR WHAT IS |
| | CURRENTLY IN UNIT 103 BUT PROPOSED TO BECOME A PART OF |
| | 104. |
| | |
| | PLEASE PROVIDE AN "EXISTING" FLOOR PLAN. NEW |
| | CONSTRUCTION NOT CLEAR. |
| | |
| | 2. LOCATION OF RATED WALLS NOT CLEAR. SHOW EXISTING |
| | RATED WALLS, PROPOSED NEW, AND PROVIDE A DETAIL (TESTED |
| | ASSEMBLY) FOR NEW RATED WALLS AND INFILL FBC 703, |
| | 709.1. SHOW EXISTING DUCTWORK AND PROPOSED DAMPERS |
| | REQUIRED BY FBC 713. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. |
| | 3RD REVIEW, IT APPEARS THAT A PORTION OF UNIT 103 WILL |
| | BECOME A PART OF UNIT 104. RESUB SHEET STATES THAT THIS |
| | WALL IS "CLEARLY SHOWN" AND "NON FIRE RATED." SEE FBC |
| | 709.19(6) AND EXCEPTIONS. IT APPEARS THAT A FIRE RATED |
| | PARTITION IS REQUIRED. |
| | |
| | 3. OK |
| | |
| | 4. PROVIDE OCCUPANT LOAD FOR PROPOSED NEW SPACE, FBC |
| | 1004. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. |
| | 3RD REVIEW, RESUB SHEET STATES THAT THIS WILL HAVE NOT |
| | MORE THAN 5 PEOPLE FOR 2382 SF. SEE FBC 1004, OCCUPANT |
| | LOAD NOT TO BE LESS THAN FBC TABLE 1004. REVISE PLAN TO |
| | INCLUDE OCCUPANT LOAD. |
| | |
| | 5. OK |
| | |
| | 6. NEW ROOMS SHOWN; REVISE PLAN TO INCLUDE ROOM |
| | DESIGNATIONS. |
| | |
| | 3RD REVIEW, NOT ADDRESSED. RESUB SHEET STATES THAT THIS |
| | IS OFFICE AND CLERICAL USE ONLY. REVISE PLAN TO INCLUDE |
| | ROOM DESIGNATIONS SO OCCUPANT LOAD CAN BE |
| | DETERMINED/CONFIRMED. |
| | |
| | NEW COMMENT: |
| | |
| | 7. RESUB SHEET STATES THAT THIS IS A LEVEL 2 |
| | ALTERATION. REVISE PLAN TO INCLUDE THIS INFORMATION. |
| | |