2013-06-03 14:05:53****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 PLEASE NOTE THAT COMMENTS SHOULD BE ADDRESSED BY
 REVISING THE PLAN TO SHOW CODE COMPLIANCE. A
 TRANSMITTAL LETTER IS HELPFUL FOR PLAN REVIEW. SOME OF
 THE COMMENTS WERE ADDRESSED WITH A PARAGRAPH ON THE
 RESUBMITTAL FORM. SEE FBC 107, PLANS TO CLEARLY SHOW
 SCOPE OF WORK AND CODE COMLIANCE.
  
 COMMENTS FROM PREVIOUS LISTS:
  
 1. IT APPEARS THAT ONE UNIT IS TO BE SPLIT INTO TWO
 UNITS. REVISE THE PLAN TO SHOW EXITING FOR UNIT 103. AS
 DRAWN, THEY NOW NEED TO EXIT THROUGH UNIT 104.
  
 2ND REVIEW, NOT ADDRESSED.
 3RD REVIEW, NOT ADDRESSED. THE RESUB SHEET STATES THAT
 104 IS NOT BEING SPLIT. IT IS NOT CLEAR HOW EXITING FOR
 103 IS AFFECTED AS THE ONLY EXIT SHOWN FOR WHAT IS
 CURRENTLY IN UNIT 103 BUT PROPOSED TO BECOME A PART OF
 104.
  
 PLEASE PROVIDE AN "EXISTING" FLOOR PLAN. NEW
 CONSTRUCTION NOT CLEAR.
  
 2. LOCATION OF RATED WALLS NOT CLEAR. SHOW EXISTING
 RATED WALLS, PROPOSED NEW, AND PROVIDE A DETAIL (TESTED
 ASSEMBLY) FOR NEW RATED WALLS AND INFILL FBC 703,
 709.1. SHOW EXISTING DUCTWORK AND PROPOSED DAMPERS
 REQUIRED BY FBC 713.
  
 2ND REVIEW, NOT ADDRESSED.
 3RD REVIEW, IT APPEARS THAT A PORTION OF UNIT 103 WILL
 BECOME A PART OF UNIT 104. RESUB SHEET STATES THAT THIS
 WALL IS "CLEARLY SHOWN" AND "NON FIRE RATED." SEE FBC
 709.19(6) AND EXCEPTIONS. IT APPEARS THAT A FIRE RATED
 PARTITION IS REQUIRED.
  
 3. OK
  
 4. PROVIDE OCCUPANT LOAD FOR PROPOSED NEW SPACE, FBC
 1004.
  
 2ND REVIEW, NOT ADDRESSED.
 3RD REVIEW, RESUB SHEET STATES THAT THIS WILL HAVE NOT
 MORE THAN 5 PEOPLE FOR 2382 SF. SEE FBC 1004, OCCUPANT
 LOAD NOT TO BE LESS THAN FBC TABLE 1004. REVISE PLAN TO
 INCLUDE OCCUPANT LOAD.
  
 5. OK
  
 6. NEW ROOMS SHOWN; REVISE PLAN TO INCLUDE ROOM
 DESIGNATIONS.
  
 3RD REVIEW, NOT ADDRESSED. RESUB SHEET STATES THAT THIS
 IS OFFICE AND CLERICAL USE ONLY. REVISE PLAN TO INCLUDE
 ROOM DESIGNATIONS SO OCCUPANT LOAD CAN BE
 DETERMINED/CONFIRMED.
  
 NEW COMMENT:
  
 7. RESUB SHEET STATES THAT THIS IS A LEVEL 2
 ALTERATION. REVISE PLAN TO INCLUDE THIS INFORMATION.
  