Plan Review Notes
Plan Review Notes For Permit 13030620
Permit Number 13030620
Review Stop B
Sequence Number 1
Notes
Date Text
2013-04-02 14:47:55****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. IT APPEARS THAT ONE UNIT IS TO BE SPLIT INTO TWO
 UNITS. REVISE THE PLAN TO SHOW EXITING FOR UNIT 103. AS
 DRAWN, THEY NOW NEED TO EXIT THROUGH UNIT 104.
  
 2. LOCATION OF RATED WALLS NOT CLEAR. SHOW EXISTING
 RATED WALLS, PROPOSED NEW, AND PROVIDE A DETAIL (TESTED
 ASSEMBLY) FOR NEW RATED WALLS AND INFILL FBC 703,
 709.1. SHOW EXISTING DUCTWORK AND PROPOSED DAMPERS
 REQUIRED BY FBC 713.
  
 3. TRAVEL DISTANCE IS SHOWN TO THE OFFICE ENTRY RATHER
 THAN TO THE OUTSIDE. EITHER REVISE TRAVEL DISTANCE TO
 INCLUDE TRAVEL TO THE EXIT DISCHARGE OR PROVIDE
 INFORMATION AS TO HOW IT HAS BEEN DETERMINED THAT THE
 LOBBY AND SPACES BEYOND ARE A RATED EXIT, FBC 1016.1.
  
 4. PROVIDE OCCUPANT LOAD FOR PROPOSED NEW SPACE, FBC
 1004.
  
 5. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1.