| Plan Review Notes For Permit 13030620 |
| Permit Number |
13030620 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-04-02 14:47:55 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. IT APPEARS THAT ONE UNIT IS TO BE SPLIT INTO TWO | | | UNITS. REVISE THE PLAN TO SHOW EXITING FOR UNIT 103. AS | | | DRAWN, THEY NOW NEED TO EXIT THROUGH UNIT 104. | | | | | | 2. LOCATION OF RATED WALLS NOT CLEAR. SHOW EXISTING | | | RATED WALLS, PROPOSED NEW, AND PROVIDE A DETAIL (TESTED | | | ASSEMBLY) FOR NEW RATED WALLS AND INFILL FBC 703, | | | 709.1. SHOW EXISTING DUCTWORK AND PROPOSED DAMPERS | | | REQUIRED BY FBC 713. | | | | | | 3. TRAVEL DISTANCE IS SHOWN TO THE OFFICE ENTRY RATHER | | | THAN TO THE OUTSIDE. EITHER REVISE TRAVEL DISTANCE TO | | | INCLUDE TRAVEL TO THE EXIT DISCHARGE OR PROVIDE | | | INFORMATION AS TO HOW IT HAS BEEN DETERMINED THAT THE | | | LOBBY AND SPACES BEYOND ARE A RATED EXIT, FBC 1016.1. | | | | | | 4. PROVIDE OCCUPANT LOAD FOR PROPOSED NEW SPACE, FBC | | | 1004. | | | | | | 5. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1. |
|