| Plan Review Notes For Permit 13030563 |
| Permit Number |
13030563 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-03-21 09:56:35 | 428 10TH STREET | | | REVISION #13030563 | | | PERMIT #13020274 | | | MASTER #12060308 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED | | | SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. | | | | | | PROVIDE A LOCAL WATERFLOW ALARM TO ALERT BUILDING | | | OCCUPANTS. | | | | | | SPRINKLER DESIGN SHALL CONFORM TO THE 2007 EDITION OF | | | NFPA 13R IN LIEU OF THE 2002 EDITION INDICATED ON THE | | | PLANS. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|