| 2013-04-06 11:59:15 | 515 NORTH FLAGLER DRIVE - SUITE #1800 |
| | PERMIT #13030512 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | REVIEW #2: FAIL COMMENT |
| | (1) RESPONSE COMMENT: FOR ISSUANCE OF A GENERAL |
| | BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA |
| | BUILDING CODE REQUIRES SEALED FIRE PROTECTION |
| | CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF |
| | 50 OR MORE AUTOMATIC FIRE SPRINKLERS. AFTER THE |
| | BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN |
| | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED |
| | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. |
| | REPEAT COMMENT - ORIGINAL COMMENT: FOR ISSUANCE OF A |
| | GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE |
| | FLORIDA BUILDING CODE REQUIRES SEALED FIRE PROTECTION |
| | CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF |
| | 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA |
| | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | REVIEW #2: PROVISO/NON-FAIL COMMENTS: |
| | (2) REPEAT COMMENT: PROVIDE DRAWING NOTE INDICATING ALL |
| | CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE |
| | REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS |
| | SHALL BE REMOVED FROM THE SITE DAILY. ALL DEMOLITION |
| | AND CONSTRUCTION AREAS SHALL HAVE "NO SMOKING" SIGNS |
| | POSTED. |
| | |
| | (3) REPEAT COMMENT: PROVIDE DRAWING NOTE INDICATING |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND |
| | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| | 500 NORTH DIXIE HIGHWAY. |
| | |
| | REVIEW #2: NEW COMMENT |
| | (4) SHEET E-2: HOLD-OPEN DOORS (NEW ELEVATOR LOBBY |
| | DOORS) REQUIRE THE AUTOMATIC RELEASING MECHANISM IS |
| | ACTIVATED BY THE OPERATION OF APPROVED SMOKE DETECTORS |
| | LISTED FOR DOOR LEAF RELEASE SERVICE PER NFPA 72. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |