| Plan Review Notes For Permit 13030510 |
| Permit Number |
13030510 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-05-01 15:05:24 | 1- REVISE ENERGY CALCULATIONS. SEC. 107.2.1 CITY | | | AMENDMENTS TO FBC. | | | A) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS ON PLANS | | | TO SHOW COMPLYING WITH ALL THE CREDITS TAKEN IN ITEM | | | #15 (CF, CV) AS REQUIRED BY SEC. 405.6 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | ***NOTE: THIS APPLIES TO THE MAIN HOUSE (CV) | | | | | | B) REVISE DOOR TYPE SHOWN ON SHEET 3 OF 5. WHERE IS THE | | | WOOD DOOR. SEE PRODUCT APPROVALS SUBMITTED. | | | ***NOTE: THIS APPLIES TO THE MAIN HOUSE. (20S.F NOT | | | .1S.F) NOT REVISED. | | | | | | C) OVERHANG DEPTH AND SEPARATION DIMENSIONS SHOWN ON | | | SHEET 3 OF 5 FOR THE WINDOWS IS INCORRECT. SEE PLANS | | | AND ELEVATIONS AND REVISE AS REQUIRED. | | | *** NOTE: THIS APPLIES TO THE MAIN HOUSE. NOT REVISED | | | | | | D) COMPLETE ALL THE INFORMATION ON TOP OF FORM; PERMIT | | | OFFICE, JURISDICTION, ETC. | | | | | | 2- ARCHITECT TO PROVIDE HIS NAME AND LICENSE NUMBER IN | | | THE THE TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF | | | FLORIDA ADMINISTRATIVE CODE. AND CHAPTER 481 FLORIDA | | | STATUTE. | | | SEC. 107.1 CITY AMENDMENTS TO FBC. (REPEAT COMMENT. NOT | | | ADDRESSED). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|