| 2013-03-27 14:54:12 | 13030510 |
| | 213 SEVILLE ROAD |
| | SFD INTERIOR RENOVATION |
| | |
| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | ELECTRICAL REVIEW COMMENTS. THE SCOPE OF ELECTRICAL |
| | WORK PROPOSED IS NOT EXACTLY CLEAR. |
| | |
| | IS THE ELECTRICAL SERVICE NEW OR EXISTING? |
| | |
| | SHOW LOCATION OF ELECTRICAL PANEL BOARDS AND |
| | DISCONNECTS WITH SAFETY CLEARANCES. NEC 110.26, 215.5 |
| | |
| | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| | SERVICE GROUND. NEC 250.94 |
| | |
| | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS |
| | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON |
| | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 |
| | |
| | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| | |
| | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW |
| | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 |
| | |
| | THE BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH |
| | CIRCUIT. NEC 210.11 (C) (3) |
| | |
| | A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE |
| | FRONT AND BACK ENTRANCE AREA. NEC 210.52 (E) (1) |
| | |
| | GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLES LOCATED |
| | IN THE STUDIO/CABANA. NEC 210.8 |
| | |
| | SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI |
| | PROTECTED. NEC 210.8 |
| | |
| | RECEPTACLES ARE REQUIRED SO THAT AT NO POINT ALONG THE |
| | FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE |
| | OUTLET AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC |
| | 210.52 |
| | |
| | PROVIDE A GROUND ROD AND GROUNDING ELECTRODE FOR THE |
| | STUDIO/CABANA ELECTRIC PANEL BOARD. NEC 250.32 |
| | |
| | |
| | ROBERT LECKY |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6718 |
| | |