Plan Review Notes
Plan Review Notes For Permit 13030498
Permit Number 13030498
Review Stop B
Sequence Number 2
Notes
Date Text
2013-05-21 12:15:182010 FBC-B TABLE 508.4 DOES NOT REQUIRE 1 HR FIRE
 BARRIER BETWEEN BUSINESS OCCUPANCY & S1 STORAGE, THE
 2010 FBC-B TABLE 508.2.5 DOES NOT INCLUDE STORAGE ROOM
 AS A INCIDENTIAL ACCESSORY OCCUPANCY ANYMORE WHERE AS
 THE 2007 FBC-B DID. FIRE CODES MAY BE A MORE STRINGENT
 CODE.
  
  