Date Text
2013-03-29 13:50:04PLANS DENIED
 1) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S.
 PAGE A-2 OF PLANS SHOW A WOOD DOOR ON AIR HANDLER
 CLOSET.
 2010 FBC (M)
 2) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS
 FOR FRESH AIR AND BATHROOM EXHAUST. CAN NOT USE MANUAL
 VOLUME DAMPER. PER 2010 FLORIDA ENERGY CODE.